Stator water Flashcards

1
Q

Auto start setpoint of the standby stator water pump

A

<20psid across the other pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Power supplies of stator water pumps

A

1B 134Z

1A 133Y

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

If one GC HX OOS, what actions required?

A

Reduce turbine power <75%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What cools the GC heat exchangers?

A

WS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Stator water DP limits in order

A

All measured across stator except auto pump start across pump.
32# Hi DP alarm
28#Normal DP
22# Low flow annunciator
20# Gen trip armed no alarm (arms 45 second timer), pump auto start (DP across pump)
18# Lo-2 flow alarm window annunciator
16# Gen trip in 45 sec if connected to grid

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Stator water conductivity details

A

High alarm 5.0 umhos
HIHI 9.5 umhos, if confirmed on local panel, manually trip turbine if P-8 trip reactor
If >1.5 umho swap to standby demin

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What does auto start light mean at pump control switch?

A

Auto start” signal and status light will energize on the opposite train pump whenever D/P across the respective train pump is < 20 psid

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Location of temperature, conductivity, pump D/P, other instruments

A

Inlet and outlet temp alarms of stator, D/P across filter, pumps, stator and demins, Conductivity at outlet of HXs (important one) and after demins.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly