Stator water Flashcards
Auto start setpoint of the standby stator water pump
<20psid across the other pump
Power supplies of stator water pumps
1B 134Z
1A 133Y
If one GC HX OOS, what actions required?
Reduce turbine power <75%
What cools the GC heat exchangers?
WS
Stator water DP limits in order
All measured across stator except auto pump start across pump.
32# Hi DP alarm
28#Normal DP
22# Low flow annunciator
20# Gen trip armed no alarm (arms 45 second timer), pump auto start (DP across pump)
18# Lo-2 flow alarm window annunciator
16# Gen trip in 45 sec if connected to grid
Stator water conductivity details
High alarm 5.0 umhos
HIHI 9.5 umhos, if confirmed on local panel, manually trip turbine if P-8 trip reactor
If >1.5 umho swap to standby demin
What does auto start light mean at pump control switch?
Auto start” signal and status light will energize on the opposite train pump whenever D/P across the respective train pump is < 20 psid
Location of temperature, conductivity, pump D/P, other instruments
Inlet and outlet temp alarms of stator, D/P across filter, pumps, stator and demins, Conductivity at outlet of HXs (important one) and after demins.