Main turbine and reheaters Flashcards

1
Q

HP turbine spins at ______ RPM, double axial flow, _____ stages in each direction. First stage is ____ blading and remaining stages _____.

A

1800 RPM
8 stages U1, 7 stages U2
Impulse; reaction

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Fourth stage extraction steam and drains are used _______ and _____.

A

in #_7A and B FW heaters.

as reheat steam in the first stage of the MSR.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Sixth stage extraction steam and drains are routed to_____.

A

_6A and B FW heaters.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Eighth stage extraction steam and drains are used in ____.

A

_5A and B FW heaters

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

LP turbine spins at ______ rpm and the steam flowpath is ______ . How many stages and what type?

A

1800 rpm
Double axial flow ‑ steam enters in center and flows outward through 10 reaction stages.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Intercept valves (closest to LP turbine) limits steam flow from MSR to LP turbine on a load rejection to prevent _______.
Reheat Stop valves provides added safety to prevent overspeed of turbine if turbine trips and ______.

A

Turbine overspeed.

intercept valves fail.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Second stage extraction steam and drains from LP turbine are routed to _______.

A

FW heaters #_4A,B,C.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Fourth stages LP turbines _______.

A

‑ FW heaters #_3A,B,C.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Sixth stages LP turbines_____.

A

‑ FW heaters #_2A,B,C.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Eighth and ninth stages LP turbines _________

A

‑ FW heaters #_1A,B,C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where do _PT-505 and 506 tap off?

A

Between 1st and 2nd stages

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Purpose of MSRs

A

Purpose – dry and superheat the HP turbine exhaust prior to use by the LP turbines in order to increase cycle efficiency and protect the low-pressure turbine blading from erosion.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

1st and 2nd stage reheat steam have startup drains. Drainage from these lines routed to condenser via crossover drains (_ES034A/B, _ES061A/B/C/D). What signals operate these valves?

A

Auto open on Turbine trip
Auto close at 27.3 psig crossover pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Cold start in AUTO sequence:

A

Controller opens leakoff valves (_MS114’s)
Controller opens purge valves (_MS067’s) at 10% load.
Opens shutoff valves (_MS009’s) and closes leak off valves (_MS114’s) at 35% load.
Verifies shutoff valves (_MS009’s) open, then begins to increase inlet steam temp at 100F/HR by opening _MS147’s first, then _MS010’s.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

_____ is design limit for turbine materials analysis.

A

550F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Reheat temperature ramps shall be limited to less than______

A

100F/hr

17
Q

LP Turbine Inlet Steam Temperature shall not exceed_____differential between turbines

A

50F

18
Q

Total loss of power to MSR controller will cause a loss of control system for AUTO and MANUAL control and the _________ will close.

A

MSR RTC valves will close

19
Q

High temp steam light will be lit when ____ and automatic action is _____.

A

Lit if LP inlet steam temp. > 550°F.
Reheat steam control valves (_MS010’s, _MS147’s) ramp back to lower LP inlet temp.

20
Q

Low load operate light maintains _____F when load is _____ for 5 minutes.

A

<425F
<10%

21
Q

Loss of a tube bundle requires it’s counterpart from _____ to be removed from service.

A

the other MSR

22
Q

Normally _____ pairs of thermocouples used for RTC with ____ as a backup.
Will shift _____ if backup lost.

A

A and C
B
manual

23
Q

Failure of any TC lights the ______.

A

TC fail light.

24
Q

MS010/147 Won’t open unless _______.

A

MS009 shutoff valves are open

25
Q

MS147A-D and _MS010A-D and some miscellaneous drain valves__________.

A

fail open on loss of IA

26
Q

Proper temperature control of MSR is required to prevent: (3 items)

A

Thermally induced damage
Excessive vibration
Excessive differential expansion

27
Q

What is the difference between hot reheat header A and B supplies?

A

Hot reheat header A supplies the steam to drive the turbine driven main feed pumps.

28
Q

Normally, the MSR drains go to _____, 1st stage reheater drains go to _____ and 2nd stage reheater drains go to_______.

A

HDT
1st stage=5a/b heaters
2nd stage=7a/b heaters