ESFAS Flashcards

1
Q

SI signals

A
  1. Manual, 1/2 switches
  2. Pzr low pressure, 1829# 2/4
  3. Steamline low pressure, 640 psig 2/3 on 1/4 SGs
  4. Cont high pressure, 3.4 psig, 2/3
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

CVI signals

A

Manual phase A
Manual CS/phase B
SI
Cnmt area high rad AR11/12J

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

FWI signals

A

SI
P14
P4 with low Tave 564F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Steamline isolation signals

A

Manual, 1/2 switches
Steamline low pressure, 640 psig, 2/3 on 1/4 SGs
Steamline high neg rate, >100 psig drop w/in 50 sec 2/3 1/4 SG
Cnmt hi-2 pressure, 8.2 psig, 2/3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

CS/Phase B signals

A

Manual 2/2 switches
Cnmt hi pressure, 20 psig 2/4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

CS/Phase B can/can not be reset with initiating signal still present

A

CAN

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which actuations can be reset with initiating signal still present?

A

Containment Phase A
Containment Phase B
CVI
Control room vent actuation (from SI)
CS actuation
P-4 with low Tave FW isolation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How to reset a FWI after a SI signal

A
  1. Reset SI
  2. Block Steamline and pzr low SI (<P-11)
  3. Cycle the rx trip breakers to clear P4 seal in
  4. Reset FWI main relays
  5. Reset the FWI auxiliary relays
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How to reset a FWI after a P-14

A
  1. Clear P-14, all steam generator levels
  2. Cycle the rx trip breakers to clear the P4 seal in
  3. Reset FWI main relays
  4. Reset the FWI auxiliary relays
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Once SI has been blocked, how can the block be removed?

A

Cycle reactor trip breakers to toggle P-4. This will unblock the SI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

If a reactor trip breaker doesn’t open with a SI, __________ until _______.

A

SI cannot be reset on that train until that RTB is opened

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Train A SSPS will de-energize ______ UV coils to open the breakers. Train B SSPS will de-energize _____ UV coils.

A

Train A, RTA and BYB UV coils
Train B, RTB and BYA UV coils

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Reactor trip bypass breaker trips

A
  1. Rx trip switch to actuate
  2. Manual SI switch to actuate
  3. Bypass breaker CS to trip
  4. UV coil de-energized
  5. Opposite train bypass breaker racked in and closed
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Reactor trip breaker trips

A
  1. Reactor trip switch to actuate
  2. Manual SI switch to actuate
  3. Shunt coil energized
  4. UV coil de-energized
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Reactor trip bypass breaker trips when in test

A

Bypass breaker CS to trip
UV coil de-energized

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Bypass breaker indication lights on PM05J lit only when _____.

A

Bypass breaker racked in with fuses installed.

17
Q

SI recirc sump isol valve reset PB will _____ and if not reset will ______.

A

Remove the auto open signal to SI 8811a/b and remove an auto signal to CV8110/8111
Prevent closure of ACB 1411

18
Q

AUTO SI BLOCKED light will be ______ if _______.

A

Fast flashing if one train wasnt blocked because of RT or bypass breaker not open

19
Q

SI can be reset After a ______ second time delay,

A

60 second