RSH supervisory Flashcards

1
Q

What is the effect of loss of master control station?

A

Equipment must be started locally

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Loss of the remote RSH panel will prevent______.

A

Interposing relays from being energized and loss of control to equipment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

There is/is not synchronization capability between RSH 4KV buses.

A

IS NOT, dead bus only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

RSH 4kv breakers normally operated from _____ and can/can not be operated locally. 480v breakers are operated from___.

A

MCR
Can be operated locally with umbilical cord
Locally only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

SX makeup pumps are/are not controlled through RSH supervisory.

A

ARE not

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

From the master to the remote station:

A

a. Master station sequentially scans MCB control switch positions
b. Control signals based on MCB switch positions
c. Control signals transmitted to the remote station on a two conductor cable
d. Circuit cards energize relays at the remote station
e. Energizing the relays close contacts in the control circuits for remotely operated equipment
f. Closing the contacts start or stop the equipment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

From the remote to the master station

A

a. Remote station sequentially scans the status of RSH equipment.
b. Status signals transmitted to the master station by the same two wire cable used to transmit the control signals
c. Status signals operate relays at master station
d. Relays operate contacts to provide MCB indications

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the only SX makeup pump related alarm that is processed by RSH supervisory?

A

Only the SX Makeup Pump DO Tank Lo annunciator uses the RSH Supervisory System

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Analog meters on MCB fail_____ when master or remote RSH supervisory lost.

A

off/low

How well did you know this?
1
Not at all
2
3
4
5
Perfectly