Control room ventilation Flashcards

1
Q

Starting interlocks
Supply____
Return____
Makeup___

A

Supply None
Return Supply fan running
Makeup 1. Supply fan running
2. Deluge valves not open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Auto starts
Supply _____
Return _____
Makeup ____

A

Supply None
Return None
Makeup 1. SI 2. Hi rad (Red1/2) PR031/32A, 33/34-0B. RM operate failure 2/2 or Loss of 1/2 power supplies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Trips
Supply ______
Return ______
Makeup _____

A

Supply 1. Fan Hi DP, 15 sec TD, 2. Deluge open, 3. Overcurrent
Return 1. Supply fan off, 2. Overcurrent
Makeup 1. Supply fan off, 2. Lo air flow (45 sec TD), 3. Deluge valve not closed, 4. Overcurrent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

High radiation signal, one of the following is required to actuate:
1.
2.
3.

A
  1. High gaseous radiation on the control room outside air intake. Either 0PR31J or 32J train A/ 0PR33J or 34J train B.
  2. Operate failure on both 31 and 32J or 33 and 34J.
  3. Loss of power to one rad monitor
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

A LOOP to ______ will result in the operating VC train restarting in ____.

A

141/142
Emergency M/U mode

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

SI sequence

A
  1. MU filter fan starts
  2. MU filter fan outlet damper modulates open to control flow.
  3. MU filter unit intake damper opens
  4. Normal intake from outside closes
  5. Recirc charcoal adsorber unisolates.
  6. Both control room WO pps and chillers receive starts signals. U1 only
    Stby train chiller only starts if cw pump running.
  7. Isolates purge dampers if open.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

SI to CR ventilation must be manually reset with _____ located_____.

A

by ESF reset PBs on PM06J to realign system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

High radiation signal must be clear to realign dampers to normal postion. This is accomplished by ____.

A

No reset PBs, high radiation signal must be clear

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

MU air bypass line used for ___, ____, or _____ in turbine building.

A

Fire, High rad, or HELB

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

A single VC Temperature Control System train will
provide the required temperature control to maintain the
control room _______.

A

<=90F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The design basis of the VC Temperature Control System is to
maintain the control room temperature for _____ of
continuous occupancy.

A

30 days

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the normal air supply for the makeup fan?

A

Turbine building

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What happens if CR purge in progress and a SI occurs?

A

Purge is terminated

How well did you know this?
1
Not at all
2
3
4
5
Perfectly