Chilled water systems Flashcards
1
Q
Control room chiller trips
A
CS to trip
UV
Overcurrent
Any chiller trip
2
Q
Control room chiller condenser SX inlet valve is ______ valve and is _____.
A
MOV
Deenergized open
3
Q
For LCO 3.7.10 and 3.7.11, must have______.
A
Two filtration and two temperature control trains.
4
Q
If a LOOP or SI occur, the control room CW system ______ and the containment CW system ____.
A
Pump and chiller auto starts 0 sec and 15/60 sec TD
Containment CW pump and chiller trip
5
Q
20 minute ______ could prevent a subsequent start.
A
anti recycle timer