Secondary water system Flashcards

1
Q

Basis for minimum CST level:

A

Maintain the RCS at hot standby conditions for 2 hours followed by a cooldown to RHR conditions at 50F/hr followed by a period not longer than one-hour to allow warmup of the RHR pumps prior to placing the RHR system into service in shutdown cooling mode.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

A MCB alarm will occur if either the ____ or the _____ are not fully closed.

A

Emergency overflow or emergency makeup valves are not fully closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Emergency makeup to hotwell ___
Normal makeup to hotwell____
Normal overflow to CST____
Emergency overflow to CST____

A

7”
14”
21”
32”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly