Fire protection Flashcards
Purpose of fire protection system:
- Early detection of fires
- Extinguish or prevent spread of fires
- Allow personnel to manually combat
- Alarms to warn personnel and allow evacuation for impending actuation
_______ or ________ between the AEER and MCR will cause a trouble wire open or fire wire open alarm.
Open circuit
Loss of supervisory current
Detectors: (3)
- Product of combustion detectors (ionization)
- Thermal detectors:
a. Rate of rise - actuates when rate of rise exceeds 15F/min
b. Continuous linear thermal sensor - used on transformers - Ultraviolet - actuates if UV detected for >3 seconds
Fire pumps and auto setpoints:
0A Jockey pump Starts 145 stops 160
0B Jockey pump Starts 140 stops 150
0A motor driven Starts 135 must be manually stopped
0B diesel driven - Starts 125 or loss of power to battery
charger, must be manually stopped
Pump power supplies:
0A Jockey 134U
0B Jockey 133U
Electric fire pump 144
Dry header/deluge (7)
- Main turbine oil reservoir
- Main turbine bearings
- H2 seal oil skids
- Transformers (MPT, UAT, SAT)
- Charcoal filters
- DG fuel oil storage tank room foam system
- Containment access facilities
CO2 systems:
B AF pump rooms
Day tank rooms
Upper cable spreading room (backup only to halon)
Lower cable spreading room
DG rooms, DG day tank rooms, and DG cable tunnels
SX makeup pump and day tank rooms
In plant CO2 suppression supplied from the ________ and has a ______additive to alert operators to leaks.
10 ton CO2 tank
Wintergreen
Unit 1 and unit 2 lower cable spreading rooms and diesel cable tunnel require _____ coincidence, one _____ and one _____ to have a co2 actuation.
2/2
heat
smoke
CO2 actuations
Auto uses _____
Manual uses______
Manual backup_____
Detectors
PB but only works if power available
Manually actuate EMPCs
Master EMPC fails _____ and zone EMPCs fail _____.
Open
Closed
Halon subsystem protects _____ and ______.
Requires ____ coincidence, one ____ and one _____.
Upper CSR and Service building QA vault
2/2 detectors (one thermal and one ionization detector)
Detector types
Ionization (Particles of Combustion)
Thermal
Ultraviolet
Fire Detection Zone 1D-6 has four alarms at Panel 1PM09J
Fire
Trouble
Fire Wire Open
Trouble Wire Open
Fire
Fire Wire Open
Trouble
Trouble Wire Open
Fire- detector actuated
Fire wire open - Open circuit or loss of supervisory between AEER and MCR
Trouble - Open circuit or loss of supervisory between field and AEER
Trouble wire - Open circuit or loss of supervisory between AEER and MCR