Purpose of fire protection system:

A
  1. Early detection of fires
  2. Extinguish or prevent spread of fires
  3. Allow personnel to manually combat
  4. Alarms to warn personnel and allow evacuation for impending actuation
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

_______ or ________ between the AEER and MCR will cause a trouble wire open or fire wire open alarm.

A

Open circuit

Loss of supervisory current

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Detectors: (3)

A
  1. Product of combustion detectors (ionization)
  2. Thermal detectors:
    a. Rate of rise - actuates when rate of rise exceeds 15F/min
    b. Continuous linear thermal sensor - used on transformers
  3. Ultraviolet - actuates if UV detected for >3 seconds
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Fire pumps and auto setpoints:

A

0A Jockey pump Starts 145 stops 160
0B Jockey pump Starts 140 stops 150
0A motor driven Starts 135 must be manually stopped
0B diesel driven - Starts 125 or loss of power to battery
charger, must be manually stopped

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Pump power supplies:

A

0A Jockey 134U
0B Jockey 133U
Electric fire pump 144

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Dry header/deluge (7)

A
  1. Main turbine oil reservoir
  2. Main turbine bearings
  3. H2 seal oil skids
  4. Transformers (MPT, UAT, SAT)
  5. Charcoal filters
  6. DG fuel oil storage tank room foam system
  7. Containment access facilities
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

CO2 systems:

A

B AF pump rooms
Day tank rooms
Upper cable spreading room (backup only to halon)
Lower cable spreading room
DG rooms, DG day tank rooms, and DG cable tunnels
SX makeup pump and day tank rooms

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

In plant CO2 suppression supplied from the ________ and has a ______additive to alert operators to leaks.

A

10 ton CO2 tank

Wintergreen

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Unit 1 and unit 2 lower cable spreading rooms and diesel cable tunnel require _____ coincidence, one _____ and one _____ to have a co2 actuation.

A

2/2

heat

smoke

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

CO2 actuations
Auto uses _____
Manual uses______
Manual backup_____

A

Detectors
PB but only works if power available
Manually actuate EMPCs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Master EMPC fails _____ and zone EMPCs fail _____.

A

Open

Closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Halon subsystem protects _____ and ______.

Requires ____ coincidence, one ____ and one _____.

A

Upper CSR and Service building QA vault

2/2 detectors (one thermal and one ionization detector)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Detector types

A

Ionization (Particles of Combustion)
Thermal
Ultraviolet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Fire Detection Zone 1D-6 has four alarms at Panel 1PM09J

A

Fire
Trouble
Fire Wire Open
Trouble Wire Open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Fire
Fire Wire Open
Trouble
Trouble Wire Open

A

Fire- detector actuated
Fire wire open - Open circuit or loss of supervisory between AEER and MCR
Trouble - Open circuit or loss of supervisory between field and AEER
Trouble wire - Open circuit or loss of supervisory between AEER and MCR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

EDG room uses flame detector for ______ and a thermal detector for_____.

A

Fire indication in MCR

CO2 suppression