Gland water system Flashcards

1
Q

FW pump seal tank level hi and low alarm setpoints

A

1 foot above and 1 foot below centerline

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

FW pump gland water DP high alarm

A

831” H20 (~ 30 psig)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

HD pump gland water inlet pressure hi and low alarms

A

340# hi
300# lo

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

CBP pump gland water inlet pressure hi and low alarms

A

183# hi
100# lo

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

CD pump gland water inlet pressure hi and low alarms

A

75# hi
5# lo

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

GW only supplies ____ to CD/CDBPs

A

Cooling

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

FWP inner seal regulator maintains what pressure and for what purpose?

A

d. Maintains 300 psig backpressure on inner seal drains
e. Prevents flashing of drains to steam

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Seal water tank to condenser LCV is a _____ operated valve and fails ___.

A

Solenoid
Closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What does gland water supply?

A

CD, CDBP (cooling only), MFP seals
Vacuum breaker loop seal
Vacuum breaker valve seal
SJAE loop seal
Off gas loop seal
Condenser block valve lantern ring
Steam dump block valve lantern ring

How well did you know this?
1
Not at all
2
3
4
5
Perfectly