Gland water system Flashcards
FW pump seal tank level hi and low alarm setpoints
1 foot above and 1 foot below centerline
FW pump gland water DP high alarm
831” H20 (~ 30 psig)
HD pump gland water inlet pressure hi and low alarms
340# hi
300# lo
CBP pump gland water inlet pressure hi and low alarms
183# hi
100# lo
CD pump gland water inlet pressure hi and low alarms
75# hi
5# lo
GW only supplies ____ to CD/CDBPs
Cooling
FWP inner seal regulator maintains what pressure and for what purpose?
d. Maintains 300 psig backpressure on inner seal drains
e. Prevents flashing of drains to steam
Seal water tank to condenser LCV is a _____ operated valve and fails ___.
Solenoid
Closed
What does gland water supply?
CD, CDBP (cooling only), MFP seals
Vacuum breaker loop seal
Vacuum breaker valve seal
SJAE loop seal
Off gas loop seal
Condenser block valve lantern ring
Steam dump block valve lantern ring