How many main steam safety valves?
What are their setpoints?
5 per steam generator
1175#, 1190#, 1205#, 1220#, 1235#
MS system purpose
- Contain and transport steam to the turbines for electrical production
- Provides for a means for removing heat from the steam generators when the turbine is not available through the use of steam dumps and atmospheric reliefs.
- Directs steam for use by:
a. HP turbines
b. MSRs 2
c. Main condenser air ejectors 2
d. TD MFWPs
e. Steam dumps 12
f. Gland sealing steam
Loads supplied by main steam:
a. HP turbines
b. MSRs 2
c. Main condenser air ejectors 2
d. TD MFWPs
e. Steam dumps 12
f. Gland sealing steam
Main steam actuation signals (5)
- Hi Hi Containment pressure=8.2 psig 2/3
- Low steamline pressure = 640 psig rate sensitive 2/3 on 1/4
- High steamline pressure rate (below P-11 and steamline pressure SI blocked) 100 psig/50 sec 2/3 on 1/4
- Manual main steam isolation 1/1 at 1/2 locations
- Individual MSIV control switches
Manually actuating main steam actuation does/does not close the MSIV bypass valves.
Does not
Governor valve opening sequence
1, 2, and 3 open at the same time and then GV 4 opens.
Which pressure transmitter provides input for SG porv operation? What is the normal lifting setpoint?
PT-041 and controls 1115-1175#
Safeties have a capacity of _____% per valve and atmospheric PORVs have a capacity of _____% per valve.
5.6%(5.65%) unit 1 (2) 112%/113%
3.3%(2.6%) Unit 1 (2) 13.2/10.4
0-100% steam pressures for both units
unit 1 1092-1006 psig
unit 2 1092-887 psig
MSIVs are controlled from MCB to ______ and RSDP to ____.
O, C, Test
O, C
MSIVs will normally open in _____, normally close in _____, emergency close in _____ and partial stroke is based on____.
5 minutes
5 seconds
2.5 seconds
Needle valve positions
MSIV bypass valve requires ____ to open and fails ____.
Air
closed
MSIV solenoid power supplies. A and D active _____ Standby ____. B and C active _____ Standby ______.
DC 111 / DC 112
DC 112/ DC 111
A level control malfunction in the main steam flash tank has the potential to _________.
Draw air into the condenser
Throttle valves control turbine speed from _____ and governor valves control speed beyond_____.
0-1700 RPM
>=1700 RPM
Each MSR is protected by 3 relief valves with setpoints _____.
250, 256, 265 psig
3 Steam line PTs per steam generator that input to: (10 items)
PT514, 515, 516
- Indication on MCB
- Indication at RSDP
- Low pressure alarm
- Recorder on PM04J
- Computer
- SI and RPS
- Density compensation
- SG WHPS (U2)
- Steam dump steam pressure mode (PT516 only)
- MS/FW header DP meter PI509
FT512 and FT513 steamline flow transmitters provide input to: (5 items)
- Indication on MCB
- Steam flow mismatch alarm
- Recorder on PM04J
- Computer input
- Input to SGWLC and FW pp speed
PT 505 and 506 are the impulse pressure instruments and provide input to: (5 items)
- P-13 turbine at power
- C-20 AMS
- Computer (P0398)
- MCB indication
- Impulse pressure validation circuitry