EDG room ventilation Flashcards
1
Q
Fire in DG room or day tank room, what happens:
A
- Both fans trip
- Dampers close
- CO2 is actuated (after time delay so people can exit)
2
Q
Purpose of system
A
- Provide DG with combustion air
- Provide class 1E HVAC to DG and auxiliaries
- Removes fumes from oil rooms
- Isolates rooms in case of fire
3
Q
High room temp limit for operating the diesel
A
Do not start or continue to run DG when room temp exceeds 132F.
4
Q
DG room supply fans are controlled from:
A
MCR only
5
Q
DG room exhaust fans are controlled:
A
Locally only
6
Q
Supply air temperature maintained at :
A
> =65F
7
Q
DG supply fan Auto Starts
A
MCR switch to start
EDG start
Temp in room >115F
8
Q
Outside air makeup temp control set at:
A
65F