EDG room ventilation Flashcards

1
Q

Fire in DG room or day tank room, what happens:

A
  1. Both fans trip
  2. Dampers close
  3. CO2 is actuated (after time delay so people can exit)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Purpose of system

A
  1. Provide DG with combustion air
  2. Provide class 1E HVAC to DG and auxiliaries
  3. Removes fumes from oil rooms
  4. Isolates rooms in case of fire
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

High room temp limit for operating the diesel

A

Do not start or continue to run DG when room temp exceeds 132F.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

DG room supply fans are controlled from:

A

MCR only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

DG room exhaust fans are controlled:

A

Locally only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Supply air temperature maintained at :

A

> =65F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

DG supply fan Auto Starts

A

MCR switch to start
EDG start
Temp in room >115F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Outside air makeup temp control set at:

A

65F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly