Digital rod position indication Flashcards
Power supply for DRPI is ______. If fails, a backup can be selected with a switch located _____.
134V1 and 133X1
426’ penetration area
Note that the ____ two coils are always penetrated and the ____two coils are never expected to be penetrated
bottom
top
Error in data A condition______
Error in data B condition______
+10, -4 steps
-10, +4 steps
Shutdown bank rods have a transition area between ____ and _____ steps. ____ is lit.
18-210 steps
Transition zone LED
Data cabinets A and B are located in the ______.
Containment Building
____ to ____ steps when Data ____ is the only good cabinet.
+10 to -4 steps
Data cabinet B
10-4 buddy
Causes of Rod Dev Pwr range tilt alarm: (4)
-2 % radial tilt or >=25% axial tilt (NIs)
-Demand >ARO, sequence or overlap >1 step deviation, CBD >223 steps
-> 12 Steps Dev w/in a bank, SD Rod < 225 (DRPI) when that bank > 227 (Demand
-DRPI Vs. Demand > 12 steps (computer)
Rod at bottom alarm will come in when _____ control bank rod bottom light lit or ______ control bank _____ light is lit.
preceding
Current rod bottom light is lit
Rod bottom alarm will come in when any control bank is ____ steps and a ______ comes in.
> =12 steps
Rod bottom light within that group comes in
There are ____ central control cards. If a central control card disagrees with the other 2, ______.
3
Automatically kicks out and does not affect system operation
Ejected rod indications
Ejected Rod Indications
-DRPI (Data A and Data B) Urgent
-Rod Control Urgent Annunciator .
-General Warning (Affected Rod)
-Rod Bottom Light (Affected Rod)
-Rod Deviation Power Range Tilt Annunciator
-Possible Power Spike from Positive Reactivity
-Pressurizer Pressure Dropping
-Pzr Level Dropping
-Rise in Charging Flow
The _____ two coils are always penetrated and the ____ two coils are never penetrated.
Bottom
Top
Group step counters are reset to zero by operating the _____.
Rod control startup switch
General warning alarm causes
- General Warning
A General Warning Alarm will be accompanied by other alarms
a. Alarm flashes when:
1) A and/or B data for any rod is defective
2) Urgent Failure Alarm is present
LCO 3.1.4 Rod alignment
All shutdown and control rods shall be OPERABLE.
AND
Individual indicated rod positions shall be within 12 steps
of their group step counter demand position.