Control interlocks Flashcards
C-1 IR high flux rod stop
Setpoint and Coincidence
1 of 2 IR 20% power w/ Hi IR flux trip unblocked
2 of 2 IR <20% to clear
Function
1. Stops outward rod movement in auto and manual. Blockable above P-10
C-2 PR flux high rod stop
Setpoint and Coincidence
1 of 4 PR >103%
Function
1. Stops outward rods in auto and manual. Bypassable at NIS panel.
C-3 OT delta T rod stop and turbine runback
Setpoint and Coincidence
2 of 4 delta T ch w/i 3% of OT delta T trip setpoint
3 of 4 >3% from setpoint stops runback
Function:
- Stops auto and manual outward rod movement
- Initiates turbine runback
C-4 OP delta T rod stop and turbine runback
Setpoint and Coincidence
2 of 4 delta T ch w/i 3% of OP delta T trip setpoint
3 of 4 >3% from setpoint stops runback
Function
- Stops outward rod movement in auto and manual
- Initiates turbine runback
C-5 Turbine low power
Setpoint and Coincidence
Validated Pimp<15% (Median PT 505, 506, median DEH Pimp)
Function
1. Stops outward rod movement in auto
C-7 Loss of turbine load
Setpoint and Coincidence
10% decrease w/i 120 seconds on 2 of 3 P imp. 505, 506, median DEH Pimp
Function
1. Arms steam dumps in Tave mode
C-8 Turbine trip
Setpoint and coincidence
2 of 3 EH pressure <1000#
or
All 4 turbine TVs closed
Function
1. Generates Reactor trip >P-8
C-9 Condenser not available
Setpoint and coincidence
1 of 3 CW pump breakers closed -and-
1C exhaust hood less than 7.0” HgA
(This coincidence clears C-9)
Function
1. Blocks normal steam dump ops. Cannot be bypassed.
C-11 CBD withdrawal limit
Setpoint and coincidence
CBD >= 223 steps (from Group 1 step counters) (Resets at 221 steps)
Function
1. Stops outward rod movement in auto.
C-16 Turbine stop loading
Setpoint and coincidence
Validated (2nd lowest) Tave <553F -OR- Tave
C-20 AMS perm
Setpoints and coincidences
2 of 2 P-imp ch >30%
Function
1. Arms AMS