RH design basis:
Include one train, two trains, CC temperature
Both trains: reduces RCS temperature from 350F to 140F within 36 hours with 5000 GPM CC flow, and CC supply temperature of 105F.
First 3 hours of C/D, CC temperature allowed to increase to 120F.
One train: Reduces RCS temperature to <200F in 44 hours.
Operate for one year following LOCA (W/ single failure)
RHR pumps ratings/classification
Mechanical seals
3000 gpm rated/5000 gpm runout
Shutoff head 200 psid
RHR pump trips
Overcurrent, ground overcurrent and UV
Over pressure protection, 8701A/B and 8702A/B cannot open unless ______. hot leg suctions from ____ and ____ hot legs.
<337#
A; C
Over pressure protection for RHR system, 5 items
<337# to open hot leg suctions Two suction reliefs 450# Two discharge reliefs 600# Arm low temp CV letdown line relief lift at 600#
RH minimum flow rate is_____ gpm. ____gpm is allowable for _____ hour per month.
500; 335; one
RH606 and 607 are the ______ valves and fail _____ on loss of instrument air.
RH618 and 619 are the _______ valves and fail _____ on loss of instrument air.
heat exchanger outlet valves and controls temperature; fails open
Heat exchanger bypass valves; fail closed
PT-____ and PT-____ feed the pressure interlock for the hot leg suction isolation valves. setpoint is _____.
403; 405; 337#
RHR pump seals are cooled by _____.
CC
RHR mini recirc auto opens when flow _____ and auto closes at ______.
<750 gpm
>1400 gpm
450 # suction relief valves relieve to the _____
HUT
450# suction reliefs are sized to relieve capacity of ______ at ______ and ______ at ______.
one cv pump, 350F
two cv pumps, 200F
RWST tech spec parameters
2300-2500 ppm
35-100F
>=89% level
Loss of either PT-403 or PT-405 will prevent _____ of a _____ on associated side.
opening; hot leg suction valve
Injection to recirc
first 6 steps
Verify sump isol open 2/4 46.7% RWST
Close RWST suctions 8812s
Close CV miniflows
Close SI miniflows
Close RHR crossties (8716A/B Isolates hot leg discharge path)
Open suction header cross tie valves (8807A/B, connnects CV and SI suction headers)
Open RH to CV and SI suction valves )SI8804A and B)