ESF/Non-ESF switchgear room, MEER, and battery room Ventilation (VX/VE) Flashcards

1
Q

Generic starts/trips of fans

A
Starts:
1. Local C/S
2. NO high ΔP across fan
3. NO ionization detection
Trips:
1. Local C/S
2. High  ΔP across fan
3. Ionization detection
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Division 11 lower cable spreading room ventilation supplied by_______ and division 12 lower cable spreading room ventilation supplied by______.

A

Aux building ventilation; CABLE SPREADING ROOM
VENTILATION FAN (WITH DIV.
12)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Loss of Offsite Power and Subsequent Power Restoration

A

All fans will restart except Non-ESF SWGR Fans

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

DIV 12/22 MEER Operations

A

1) Supply fan runs continuously
2) Temp Control Dampers do not modulate
3) Two Modes of operation:
- Outside Air - at 80F, outside air damper opens and
recirc closes
- Recirc - at 70F outside air damper closes and recirc
opens
4) Exhaust Fan starts at 80F increasing and stops at 70F
decreasing
- Control Switch must be kept in “After Stop” for fan to
cycle automatically on temperature

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

To Reset from High Fan ΔP

A

-Take local control switch to
PULL OUT
-Fans normally controlled locally

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Fire in any room will:

A

1) Trip associated fan
2) High temp in room causes fire
dampers to drop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Purge Switch Actions

A
  • Fails recirc damper closed
  • Fails outside air damper open
  • Bypasses ionization trip
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

ESF Supply fans can be operated from _________
Non-ESF supply fans can be operated from________
Exhaust fans can only be operated ________

A

MCR or locally; locally; locally

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Exhaust fan supplied for each battery room to maintain hydrogen concentration <_____

A

2%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Where do most ESF vent systems draw in outside air?

A

Supply air to each system is from respective D/G Outside Air Intake, except SXCT which has its own outside air intake for each substation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Battery room admin temperature limit is:

A

> =65F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How is temperature controlled ? (Except division 12 meer)

A

Room temp is controlled by modulating the amount of air recirc’d to the amount that is supplied from outside via motor operated dampers.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Div 11 esf swgr plenum/fan also supplies______; Uses ____ for temp control.

A

Div 11 MEER; Mixed air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Div 11 MEER exhaust fan must run whenever supply fan is running to prevent________.

A

Higher pressure in Div 11 MEER relative to MCR.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

TLCO 3.7.d area temp monitoring

A

Room temp limits shall not be exceeded >8 hours, or by >30F whenever affected area equipment is required to be operable.

108F for rooms with this system.

How well did you know this?