ESF/Non-ESF switchgear room, MEER, and battery room Ventilation (VX/VE) Flashcards
Generic starts/trips of fans
Starts: 1. Local C/S 2. NO high ΔP across fan 3. NO ionization detection Trips: 1. Local C/S 2. High ΔP across fan 3. Ionization detection
Division 11 lower cable spreading room ventilation supplied by_______ and division 12 lower cable spreading room ventilation supplied by______.
Aux building ventilation; CABLE SPREADING ROOM
VENTILATION FAN (WITH DIV.
12)
Loss of Offsite Power and Subsequent Power Restoration
All fans will restart except Non-ESF SWGR Fans
DIV 12/22 MEER Operations
1) Supply fan runs continuously
2) Temp Control Dampers do not modulate
3) Two Modes of operation:
- Outside Air - at 80F, outside air damper opens and
recirc closes
- Recirc - at 70F outside air damper closes and recirc
opens
4) Exhaust Fan starts at 80F increasing and stops at 70F
decreasing
- Control Switch must be kept in “After Stop” for fan to
cycle automatically on temperature
To Reset from High Fan ΔP
-Take local control switch to
PULL OUT
-Fans normally controlled locally
Fire in any room will:
1) Trip associated fan
2) High temp in room causes fire
dampers to drop
Purge Switch Actions
- Fails recirc damper closed
- Fails outside air damper open
- Bypasses ionization trip
ESF Supply fans can be operated from _________
Non-ESF supply fans can be operated from________
Exhaust fans can only be operated ________
MCR or locally; locally; locally
Exhaust fan supplied for each battery room to maintain hydrogen concentration <_____
2%
Where do most ESF vent systems draw in outside air?
Supply air to each system is from respective D/G Outside Air Intake, except SXCT which has its own outside air intake for each substation
Battery room admin temperature limit is:
> =65F
How is temperature controlled ? (Except division 12 meer)
Room temp is controlled by modulating the amount of air recirc’d to the amount that is supplied from outside via motor operated dampers.
Div 11 esf swgr plenum/fan also supplies______; Uses ____ for temp control.
Div 11 MEER; Mixed air
Div 11 MEER exhaust fan must run whenever supply fan is running to prevent________.
Higher pressure in Div 11 MEER relative to MCR.
TLCO 3.7.d area temp monitoring
Room temp limits shall not be exceeded >8 hours, or by >30F whenever affected area equipment is required to be operable.
108F for rooms with this system.