Where are controls for 0B train VC located outside MCR?
364’ M-22 beneath the RSDP
Which equipment will not cause a MCR alarm when its RSDP switch taken to ‘local’?
MSIV
CRDM exhaust fans
CV121
RSDP panel trouble on;
Loss of 125VDC or IA pressure low 78#
In ‘local’ pressurizer heaters will trip off at _____.
<17%
Power supplies to modules of RSDP:
1pl04j DC 111
1pl05j DC 112
1pl06j DC 114
If any channel on 1pl10j is taken to fire, what happens?
Taking any hand switch to “fire” removes its associated transmitter input to RPS, MCB, RSDP, and auto control.
What will happen if the control power switch is taken to “off”?
NIs still indicate even if “off” is selected. Other indications only available if switch in the div11 or div12 positions.
Which instruments are associated with the 6 normal/fire switches?
PT-455 pressurizer pressure
PT-514 SG 1a pressure
PT-525 SG 1b pressure
LT-459 PZR level
LT-501 SG 1a level
LT-502 SG 1b level
When a Normal/Fire switch is taken to fire, what happens to control room indication?
Fails low, trips bistables
What mode is RSDP designed for?
Mode 3, to get down to mode 5
What controls do not have a local switch on RSDP?
CV oil pump
RCP trip pushbuttons
What components are on u1 RSDP but not u2?
oA VC
SX makeup pumps