Seismic Monitoring Flashcards
1
Q
What is the P.S. to the basic and supplimental motion recorders?
P.S. to Earthquake force monitor (Seismic Instrument Rack)?
P.S. to Rx Seismic Trip System?
A
Basic and supplimental - PY-14 each has internal batt b/u
Earthquake force monitor - PY-13
Rx Seismic Trip System - PY-11, 12, 13
2
Q
What will activate Basic motion recorders?
What will activate Supplimental motion recorders?
A
basic
- any basic > 0.01 g = individual starts
- common > 0.01 g (ESTA01 or 28) = all basic start
Supplimental
- any supplimental > 0.008 g = individual starts
- common > 0.008 g (ESTA20 and 27) = all supp start
- cross, ESTA01 or 28 = all basic and supp start
3
Q
How many motion recorders/ accelorometers are in the following subsystems of Seismic Monitoring?
Basic
Supplimental
Siesmic trip
A
Basic - 6
Supplimental - 13
Trip - 3