What is the purpose of the Post Accident Monitoring System (PAMS) ?
A
- provide reliable information to operators and emergency plan managers for assessment of plant conditions during and after an accident
2
Q
What are the only controls that are on PAMS panels ?
A
head vent valves
8078 A, B, C, D
3
Q
What are the different items on PAMS ?
A
PAM1
- Lacc
- Radwaste
- CNMT cooling
- gamma metrics
- RVLIS
- CET
- SCMM
- CNMT lvl, rad, H2, Press
PAM2
- rad FHB, CNMT, PV, PV room
PAM3/4 (Trn A/B)
- CET
- RVLIS
4
Q
Do PAMS indications require alignment to perform their functions?
A
no, all PAMS indications always provide indications with the exception of CNMT H2 monitors (CEL 82 and 83)
5
Q
What are some characteristics of a PAMS indication?
A
- Key parameter
- sufficient range for accident
- Capable of operating in harsh environments
- when necessary, diverse indications available