Purpose of ASW?

Basic flowpath?

Alignment?

A
  • Remove heat from CCW and reject to UHS
  • intake (bar rack, traveling screen), pump suction, hx inlet valves, CCW hx, outlet valves, CWS-> outfall
  • one pump man/on, other stby/off, flow through one hx
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Automatic starts for ASW pumps?

What starts require switch in auto?

A
  • xfr to SU (10 sec delay)
  • xfr to DG (10 sec delay)
  • SI (22 sec delay)
  • lo header pressure (40.5 psig) *
  • UV on opposite bus *
  • requires switch in auto
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Automatic trips of ASW pumps

A
O.C.
Load shed (4kv UV)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is only common failure that could take out both ASW pumps?

How is this prevented?

A

Common floor drain header => flooding in one pump room can go through drains and flood other room

  • Back flow check valves installed in drain lines
  • alarm @ 6” level
  • design level 6’ (motor height)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How is ASW pump motor able to breath since its in a watertight room?

A
  • exhaust fan on anytime pump bkr closed
  • intake and exhaust goes through ventilation shaft to outside
  • vent shaft, 49.5’ elevation, with protected structure (waves)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is purpose of ASW-601, where is it controlled from?

A

Crosstie between units, allows one unit to supply other ASW

U-1 MCR (480v 1F)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the air bottles in the CCW hx room there for?

A

The inlets to the CCW hx (ASW side) are air close, fail open valves.
If instrument air lost (100#) the bottles provide backup air to maintain valves closed so the in service CCW hx isn’t robbed cooling flow (8 hrs)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Precautions and limitations for ASW

A
  • do not fully close outlets to CCW hx (ASW side)
  • always ensure she’ll side Press (CCW ) > tube side
    So ASW doesn’t leak in
  • starting/ stopping ASW pump may cause auto start opposite unit ASW pump (low pressure)