ASW Flashcards
Purpose of ASW?
Basic flowpath?
Alignment?
- Remove heat from CCW and reject to UHS
- intake (bar rack, traveling screen), pump suction, hx inlet valves, CCW hx, outlet valves, CWS-> outfall
- one pump man/on, other stby/off, flow through one hx
Automatic starts for ASW pumps?
What starts require switch in auto?
- xfr to SU (10 sec delay)
- xfr to DG (10 sec delay)
- SI (22 sec delay)
- lo header pressure (40.5 psig) *
- UV on opposite bus *
- requires switch in auto
Automatic trips of ASW pumps
O.C. Load shed (4kv UV)
What is only common failure that could take out both ASW pumps?
How is this prevented?
Common floor drain header => flooding in one pump room can go through drains and flood other room
- Back flow check valves installed in drain lines
- alarm @ 6” level
- design level 6’ (motor height)
How is ASW pump motor able to breath since its in a watertight room?
- exhaust fan on anytime pump bkr closed
- intake and exhaust goes through ventilation shaft to outside
- vent shaft, 49.5’ elevation, with protected structure (waves)
What is purpose of ASW-601, where is it controlled from?
Crosstie between units, allows one unit to supply other ASW
U-1 MCR (480v 1F)
What are the air bottles in the CCW hx room there for?
The inlets to the CCW hx (ASW side) are air close, fail open valves.
If instrument air lost (100#) the bottles provide backup air to maintain valves closed so the in service CCW hx isn’t robbed cooling flow (8 hrs)
Precautions and limitations for ASW
- do not fully close outlets to CCW hx (ASW side)
- always ensure she’ll side Press (CCW ) > tube side
So ASW doesn’t leak in - starting/ stopping ASW pump may cause auto start opposite unit ASW pump (low pressure)