12 kV Elec System Flashcards
What does the load tap changer do?
How much will one “tap” change voltage?
What is no load voltage maintained at?
What is the load voltage maintained at?
Controls voltage output of 12 kV SU bus by changing number of windings stepping down voltage from 230 kV
300 volts
129V on meter( both 12kv S/U feeder breakers open)
120v on meter(either 12kv S/U feeder to 12kv Bud D or E closed)
What are loads off of 12 kV underground loop?
Temp air comp SWRO Met twr FW pmp house Sim bldg Maint trng bldg Admin bldg Cold mach shop Warehouse Ionics WHAT facility Package boiler B/U met twr
Normal alignment operation?
12kv buses will be supplied by the Main Gen through Aux Transformer 1-1(2-1)
12kv alignment for short term shutdown
In an event of a unit shutdown or trip, the 12kv buses are either manually or automatically shifted to the Startup Bus
-the SU Bus is normally energized by the 230kv switchyard through the OCB-212 and SU Transformer 1-1 (2-1)
Longer term shutdown operation
during longer term shutdowns, as soon as practical following a shutdown, or when the 230kv power is not available, the 12kv system can be powered by backfeeding from the 500kv switchyard
-the main gen MOD is opened
- power is supplied from the switchyard through the generator output breakers 532(542) and/or 632(642)
-500kv stepped down to 25kv by the main transformer and then to 12kv by the aux transformer 1-1(2-1)
SUT 1-1/1-2 protection
Trip switcher and 12kv S/U Bus Feeder Breaker on:
-phase overcurrent
-Differential
-sudden pressure
SUT 1-1/2-1 backup protection
If fault still exists, trip open OVB-212 and other unit 12kv S/U bus feeder breaker
What happens when the control handle is pulled out in manual?
S/U power is Inoperable
What does the 12kv S/U bus feed?
-12kv Buses D and E
-Non-Vital 4kv Buses D and E
-Vital 4kv Buses F,G, and H
-Underground Distribution (Construction loop)
12kv S/U Bus protection
-Bus under voltage(<70%)
->actuates ok 19-04
-Bus differential Current
->trips and locks out the affected S/U Bus
-> trips all 12kv Breakers
- Breaker overcurrent
-> trips breaker with fault
Startup transformer 1-2(2-2) protection
Trips and lockouts 12kv and 4kv breakers on
-overcurrent
-sudden pressure
-Differential
12kv Buses D and E bus protection
-Undervoltage(<68%)
-> trips CWPs and RCPs
-Differential
->trips supply breakers
-> prevents auto transfer to S/U bus by locking out S/U bus feeder breaker
->Trips CWPs and RCPs
12kv Bus D and E reactor protection
-undervoltage (<68%)
-> Reactor trip > p-7 (1/2 sensors 2/2 buses)
-> TDAFWP Auto Start (1/2 sensors 2/2 buses)
-underfrequency (54hz)
-> Reactor trip > p-7 (2/3 sensors 1/2 buses)
-> Trip RCP breakers associated with the bus
230kv circuit switchers purpose
Allows removal of SUT from service for maintenance without tripping the upstream breaker