DFWCS Flashcards

1
Q

What are the different modes of DFWCS?

When do they take affect?

What is main difference?

A

Low power mode & Hi power mode

Up power - @ 25% switches to Hi power mode
Down power- @ 15% switches to Lo power mode

Hi power compares Lvl setpoint vs. lvl act & stm flow vs. feed flow

Lo power doesn’t use stm & feed flows due to inaccuracies @ low power, instead uses WR S/G lvl

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is arbitration? What signals use arbitration in DFWCS?

A

A method of signal validation for parameters that

  • use only two inputs
  • use a separate parameter that can infer what monitored parameter should be

Stm flow arbitration sig = Pimp
Fd flow arbitration sig = total error (fw demand)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Describe purpose of DFWCS valve linearization and sequencing logic?

What is sequence of valves opening on up power?

A

Open FRV and bypass valves based on

  • flow demand (error)
  • valve throttling characteristics (flow,…)
  • pressure drop across valve (Psg vs. Pfw)
  • BPV opens at low power
  • @ 60% BPV position, FRV starts open
  • @ 100% BPV position, FRV @ 16%
  • BPV starts close, FRV continues open
  • @ 30% flow, BPV closed, FRV throttled
  • @ 100% flow, FRV position @ 60%
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How does DFWCS control MFP speed?

Why designed like this?

A
  • program ramp on delta P (Psg vs. Pdisch fwp)
  • 74 psid @ 0-20% —>185 psid @ 100% stm flw
  • if delta P low, speed of pump increased=> Pfw inc
  • if delta P hi, pump speed reduced=> Pfw lowered

@ higher flows, more head losses=>need more d/p to get fw to SG’s
@ lo flows, minimize erosion by lowering d/p

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Inputs to Hi power mode of DFWCS?

A
Pimp
   - PT-505A,506A,8 (med select)
   - input to program lvl (old system ramp lvl)
   - arbitrator sig for steam flow
Ls/g
   - LT-517,518,518 (med select)
   - vs. program lvl
Tfw 
   - TT-1189,1190,1191 (med select)
   - temp compensation for lvl error (shrink & swell)
Fstm 
   - FT-512,513 (arbitrated w/ Pimp)
   - vs. Ffw
Ffw
   - FT-510,511 (arbitrated w/ total error)
   - vs. Fstm 
Ps/g
   - PT-514,515,516 (med select)
   - avg of all loops
   - density compensation for steam flow
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Inputs to Lo power mode of DFWCS

A
Pimp
   - PT-505A,506A,8 (med select)
   - input to program lvl (old system ramp lvl)
Ls/g (NR)
   - LT-517,518,518 (med select)
   - vs. program lvl
Tfw 
   - TT-1189,1190,1191 (med select)
   - temp compensation for lvl error (shrink & swell)
Ls/g (WR)
   - LT-501
   - anticipatory signal...?
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Inputs to valve linearization & sequencing logic

A
Ps/g
   - PT-514,515,516 (med select)
   - all loops averaged
   - vs. Pfw for d/p signal
Pfw
   - PT-508,508A,508B (med select)
   - vs. Ps/g for d/p signal
How well did you know this?
1
Not at all
2
3
4
5
Perfectly