DFWCS Flashcards
What are the different modes of DFWCS?
When do they take affect?
What is main difference?
Low power mode & Hi power mode
Up power - @ 25% switches to Hi power mode
Down power- @ 15% switches to Lo power mode
Hi power compares Lvl setpoint vs. lvl act & stm flow vs. feed flow
Lo power doesn’t use stm & feed flows due to inaccuracies @ low power, instead uses WR S/G lvl
What is arbitration? What signals use arbitration in DFWCS?
A method of signal validation for parameters that
- use only two inputs
- use a separate parameter that can infer what monitored parameter should be
Stm flow arbitration sig = Pimp
Fd flow arbitration sig = total error (fw demand)
Describe purpose of DFWCS valve linearization and sequencing logic?
What is sequence of valves opening on up power?
Open FRV and bypass valves based on
- flow demand (error)
- valve throttling characteristics (flow,…)
- pressure drop across valve (Psg vs. Pfw)
- BPV opens at low power
- @ 60% BPV position, FRV starts open
- @ 100% BPV position, FRV @ 16%
- BPV starts close, FRV continues open
- @ 30% flow, BPV closed, FRV throttled
- @ 100% flow, FRV position @ 60%
How does DFWCS control MFP speed?
Why designed like this?
- program ramp on delta P (Psg vs. Pdisch fwp)
- 74 psid @ 0-20% —>185 psid @ 100% stm flw
- if delta P low, speed of pump increased=> Pfw inc
- if delta P hi, pump speed reduced=> Pfw lowered
@ higher flows, more head losses=>need more d/p to get fw to SG’s
@ lo flows, minimize erosion by lowering d/p
Inputs to Hi power mode of DFWCS?
Pimp - PT-505A,506A,8 (med select) - input to program lvl (old system ramp lvl) - arbitrator sig for steam flow Ls/g - LT-517,518,518 (med select) - vs. program lvl Tfw - TT-1189,1190,1191 (med select) - temp compensation for lvl error (shrink & swell) Fstm - FT-512,513 (arbitrated w/ Pimp) - vs. Ffw Ffw - FT-510,511 (arbitrated w/ total error) - vs. Fstm Ps/g - PT-514,515,516 (med select) - avg of all loops - density compensation for steam flow
Inputs to Lo power mode of DFWCS
Pimp - PT-505A,506A,8 (med select) - input to program lvl (old system ramp lvl) Ls/g (NR) - LT-517,518,518 (med select) - vs. program lvl Tfw - TT-1189,1190,1191 (med select) - temp compensation for lvl error (shrink & swell) Ls/g (WR) - LT-501 - anticipatory signal...?
Inputs to valve linearization & sequencing logic
Ps/g - PT-514,515,516 (med select) - all loops averaged - vs. Pfw for d/p signal Pfw - PT-508,508A,508B (med select) - vs. Ps/g for d/p signal