RHR Flashcards
RHR-8700A(B)….what is it?
Interlocks?
Purpose o interlocks
- RHR pump suction valves
- cannot open unless SI-8804A(B), SI-8982A(B) and CS-9003A(B) are closed
- 8982….drain RWST to floor (CNMT recirc sump)
- 9003….spray cnmt with hot RCS
- 8804….X-conn SI suct
RHR8701……what is it?
Interlocks …..?
Why……?
Normal connection RCS HL(4) to RHR
- cannot open unless Prcs < 390 psig & vap temp < 475 deg(Pzr stm)
- prevent over pressurizing RHR w/RCS
RHR-8702…….what is it?
Interlocks…..?
Why………..?
Normal connection RCS hL (4)->RHR
- cannot open unless Prcs < 390 psig
- prevent over pressurizing RHR w/RCS
Sources of water to RHR pumps?
RWST
CNMT recirc sump
RCS hL 4
RHR Pump auto starts
SI signal
RHR pump Auto Stop
Overcurrent
Transfer to Diesel
RWST <33% (2/3 coincidence)
-defeated if 8982a/b is open
-defeated if in local at breaker
-bypassed by RWST low level trip test switch (csr) for filling the refueling cavity
RHR shutoff head, design flow, runout flow
173 psid
3000 gpm
4500 gpm
RHR place in service
<350F (Mode 4)
<390 psig
Interlocks to open 8700A/B (RHR pump isolation)and why?
To Open
-8982A/B closed
-9003A/B closed
-8804A/B closed
To prevent transferring water to CVCS,Spray,or Sump during normal ops
8701/8702 (RCS Loop 4 HL Suction Isolation and why the interlocks
To open 8701
-pt-405a<390 psig
-pzr steam space <475F
To open 8702
-pt-403a <390 psig
Interlocks to prevent rhr over pressurization
Normally power removed, during shutdown power on in case closure needed for inter-system LOCA
FCV-641A/B RHR P Recirc Valves open and close at what flow
Open at <728 gpm
Close at >1398 gpm
HCV-638/637/670 RHR Flow Control & HX Bypass valves fail and have what thats special
fail open and have mechanical stops to prevent RHR Pump Runout
8809A/B RHR to Cold Legs have what special feature
series contactors to prevent inadvertent operation
8716A/B RHR Discharge Cross Tie are in what position and why
normally open to allow one RHR PP to feed all four cold legs
HCV-133 RHR HX Outlet to CVCS Letdown is used when?
When RCS pressure is too low to provide sufficient flow through normal letdown