ABVS Flashcards

1
Q

L/U for building only (ABVS)?

A
  • selected fan (S-31 or S-32) running
  • Supplied
    • buildings AB
    • CCP 1-3 room
  • exh
    • ECCS pump rooms
    • buildings AB
    • CCP 1-3
    • CCW pump rooms
  • exh - roughing filter (E-2) - x conn to E-1
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

L/U for buildings and safeguards (ABVS)?

A

both fans (S-31 & S-32) on

  • supply
    • most buildings
    • eccs pump rooms
    • CCP 1-3 pump room
    • CCW pump room
    • RHR hx room
  • exh
    • most building
    • eccs pump rooms
    • CCP 1-3 pump room
    • CCW pump room
    • RHR hx
    • CS

through roughing & hepa filters (E-2)

disch (E-1 & E-2) via x-conn

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

L/U for safeguards only (ABVS)?

A

selected fan (S-31 or S-32)

  • supply
    • eccs pump room
    • CCP 1-3 pump room
    • CCW pump room
    • RHR hx room
  • exh
    • eccs pump room
    • rhr hx room
    • CS pump room
    • CCW pump room

through roughing & HEPA filter in E-2

disch selected fan (E-2 or E-1, via x-conn)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Difference between buildings & safeguards w/S signal vs. w/o S signal?

A

S signal

  • disch of eccs, CS, ccw, RHR hx room put through charcoal filter and HEPA via E-1
  • rest of loads still go through roughing and HEPA on E-2 via E-2 (some bldg, CCP 1-3)

No S signal

  • all loads go through roughing and HEPA on E-2 via E-1 & 2(x-conn)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Difference between safeguards only w/S signal vs. w/o S signal?

A

S signal

  • all loads go through charcoal filter on E-1, via selected fan

No S signal

  • all loads go though roughing and HEPA on E-2 via selected fan
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What does POV-1 & 2 do?

A

Provide control logic for FHB and ABVS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What does status reset switch do?

A

Causes logic circuits to reset….. - switch positions - selected equipment - selected mode - current conditions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What will fan reset button do if pressed?

A

All fans will stop Modes will have to be reset (If eccs pump running, fan will not stop and system will op in B & S mode)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What will selecting S signal test do if selected? If take switch to reset?

A

Place ABVS in B & S mode w/ S signal Place ABVS in B & S mode

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How can you tell if damper or fan out of position per mode?

A

POV-1 & 2, HMI (VB-4), VB-4 status panel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

If ABVS in B & S mode…..E-1 trips….what happens?

A

Shifts to SGO mode

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

If in BO mode what will shift ABVS-> BSG mode? If signal goes away, will ABVS shift back automatically?

A
  • SI signal - any eccs pump starts (RHR, CCP, SI, CS) - manually selected (VB-4) - S signal test switch Yes, to whatever mode is selected
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Required conditions for supply fan start? What will start non selected fan?

A

Disch damper open Inlet damper closed Exh fan running Selected fan fails….30 sec low flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What will S/d supply fan in ABVS?

A
  • low flow < 90% ( > 90 sec after start) - loss control power - fan reset ( unless eccs pump on) - disch damper not fully open - exh fan trips …..after 30 sec delay
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Auto S/d of exh fans in ABVS?

A
  • low flow < 90% (> 90 sec after start) - loss control power - fan reset pushed ( unless eccs pump on) - associated mode dampers not in req positions
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the logic between having some dampeners in parallel vs. series?

A

Dampeners in series need to close Dampeners in parallel need to open