HSDP, DSDP Flashcards

1
Q

What condition is the HSDP designed to

“maintain”

and

“acheive”

What controls for the Pzr PORVs are available at the HSPD?

A

maintain - hot standby

achieve - cold shutdown w/in 72 hours

emergency close - in case fire in CR or cable spreading room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How do you transfer control of a 4kv pump to HSDP?

Does anything happen to pump auto features when control is transfered to HSDP?

What happens when auto/manual switch in HSDP taken to manual

A

transfer device on 4kv bkr to “HSDP”

all non-T.S. related auto starts are disabled on pump (also all associated lights in CR extinguish)

all auto starts are disabled on pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How do you transfer control of a 480 v load to the HSDP?

How do you transfer control back to CR?

A

take “local/ CR” to LOCAL

take “cutin/cutout” toggle switch to CUTIN

take “local/ CR” to CR

take “lockout relay” to RESET

(cutin/ cutout could be in any position)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Why are only half of the 480 v transfer relay toggle switches taken to cutin?

A

in the case of a fire in the HSDP you wont lose control of all the loads in the CR