Mn Gen H2 and CO2 Flashcards

1
Q

Why use H2 gas to cool Generator?

A

Low windage losses - less friction => less heat generated High thermal conductivity - transfers heat well Cheap

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How many different sources can we supply H2 and CO2 to Generator?

What does H2 system provide gas to?

A

H2- two, bulk supply, H2 bottles

CO2- two, cardox, CO2 bottles

Generator and cover gas to SCCW head tank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Major components and purposes of Generator H2 and CO2 system?

A

PGA(Generator auxiliary panel)- monitors H2 purity, pressure, flow

GCM(Generator condition monitor)- monitors for insulation breakdown inside Generator

Gas dryer- drys H2 gas to minimize, insulation contamination, shorts, corrosion

Level switches- check for accumulation of liquid in Generator (oil HSS operated incorrectly), leaks in H2 coolers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What do you do if you have excess H2 leakage from Main Generator?

What must Generator H2 pressure always be above?

A
  • excess H2 leak-> Trip unit, purge Generator w/CO2
  • Generator H2 Press > SCCW Press by 5 #
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What manifold used to fill Generator with H2? CO2?

A

H2- filled from top, CO2 drains from bottom, purity measured from bottom CO2- filled from bottom, H2 drains from top, purity measured from top

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What promotes the H2 gas to flow past the gas dryer?

A

The d/p caused by the internal fans inside the Generator assisted by gas dryer blowers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly