Mn Gen H2 and CO2 Flashcards
Why use H2 gas to cool Generator?
Low windage losses - less friction => less heat generated High thermal conductivity - transfers heat well Cheap
How many different sources can we supply H2 and CO2 to Generator?
What does H2 system provide gas to?
H2- two, bulk supply, H2 bottles
CO2- two, cardox, CO2 bottles
Generator and cover gas to SCCW head tank
Major components and purposes of Generator H2 and CO2 system?
PGA(Generator auxiliary panel)- monitors H2 purity, pressure, flow
GCM(Generator condition monitor)- monitors for insulation breakdown inside Generator
Gas dryer- drys H2 gas to minimize, insulation contamination, shorts, corrosion
Level switches- check for accumulation of liquid in Generator (oil HSS operated incorrectly), leaks in H2 coolers
What do you do if you have excess H2 leakage from Main Generator?
What must Generator H2 pressure always be above?
- excess H2 leak-> Trip unit, purge Generator w/CO2
- Generator H2 Press > SCCW Press by 5 #
What manifold used to fill Generator with H2? CO2?
H2- filled from top, CO2 drains from bottom, purity measured from bottom CO2- filled from bottom, H2 drains from top, purity measured from top
What promotes the H2 gas to flow past the gas dryer?
The d/p caused by the internal fans inside the Generator assisted by gas dryer blowers