Describe basic lineup and description of FHBV

A

Two supply fans, one running, one stby (S-1, S-2)

mode dampers

loads

three exhaust fans, E-4 normally running (no charcoal filter)

E-5 and 6 iodine removal fans (have charcoal filters)

all exhaust fans have roughing and hepa filters

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

what will happen to FHBV if RE-58 or 59 alarm on Hi Radiation?

A

E-4 will shutdown

E-5 or 6 will start (whichever one is selected)

Mode dampers will reposition

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the different ways to put FHBV in iodine removal mode?

A

select iodine removal mode on VB-4

Hi-Rad on RE-58 or 59

depress iodine removal mode pushbutton on SFP deck

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

what is the apppximate flowrate of the FHBV supply fans when compared to the exhaust fans? Why?

A

supply ~ 23,000 cfm

exhuast ~ 35,000cfm

normally one of each running, keeping a negative pressure on FHB

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

FHBV supply fan trips

FHBV exhaust fan trips

A

Supply

  • flow < 90%
  • loss control power to POV (125 vdc)
  • fan reset pushed
  • no exhaust fan running
  • mode damper not fully open

exhaust

  • flow < 90%
  • loss control power to POV (125 vdc)
  • fan reset pushed
  • mode damper not fully open
  • normal mode (E-5 or 6)
  • iodine mode (E-4)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Power Supplies to FHBV fans

A

S-1 G (ghost)

S-2 H (house)

E-4 (non-vit, 12N)

E-5 F (freaky)