CFCU Flashcards

1
Q

Auto start signal to CFCU

A

SI
Xfr to S/U
Xfr to diesel

All to slow speed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How does leak detection feature in CFCU’s work?

A

Fan must be in slow, only select one fan at time

  • once selected solenoid valve closes on vert run
  • when hi lvl alarm comes in start timer
  • when hi-hi lvl alarm comes in stop timer and quantify leak rate (<6 min=> …..LR > 0.25 gpm)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Purpose of ARRD’s

A

Backdraft dampers leaked by, allowing fans to rotate in reverse (higher starting current), and robbed important loads cooling====>ARRD installed to prevent fans from rotating in reverse (on motor coupling)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How does CCW interface with CFCU’s?

A

1950 gpm to cooling coils(ATM cooling)

50 gpm to motor cooler (sealed casing to protect and cool motor from harsh environment(accident))

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Design features/ functions of CFCU’s

A

Mix CNMT air(H2….radioiodine)( normal vent)
Maintain CNMT air<120 deg(won’t ovrprs cnmt or Damage elec equip)(personnel protection)
Limit Pcnmt < 47 psig(2 CFCU’s & one spray train)
Provide leak indication

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

P.S. to CFCU’s

A
1-F
2-F
3-G
4-H
5-G
How well did you know this?