CFCU Flashcards
Auto start signal to CFCU
SI
Xfr to S/U
Xfr to diesel
All to slow speed
How does leak detection feature in CFCU’s work?
Fan must be in slow, only select one fan at time
- once selected solenoid valve closes on vert run
- when hi lvl alarm comes in start timer
- when hi-hi lvl alarm comes in stop timer and quantify leak rate (<6 min=> …..LR > 0.25 gpm)
Purpose of ARRD’s
Backdraft dampers leaked by, allowing fans to rotate in reverse (higher starting current), and robbed important loads cooling====>ARRD installed to prevent fans from rotating in reverse (on motor coupling)
How does CCW interface with CFCU’s?
1950 gpm to cooling coils(ATM cooling)
50 gpm to motor cooler (sealed casing to protect and cool motor from harsh environment(accident))
Design features/ functions of CFCU’s
Mix CNMT air(H2….radioiodine)( normal vent)
Maintain CNMT air<120 deg(won’t ovrprs cnmt or Damage elec equip)(personnel protection)
Limit Pcnmt < 47 psig(2 CFCU’s & one spray train)
Provide leak indication
P.S. to CFCU’s
1-F 2-F 3-G 4-H 5-G