AFW Flashcards

1
Q

What S/G’s does terry turbine supply?

AFW pump 1-2?

AFW pump 1-3?

Via what valves?

A

TT, 1-4 (LCV-106, 107, 108, 109)

1-2, 1,2 (LCV-110, 111)

1-3, 3,4 (LCV-115, 113)

Via cross connect, each MDAFW pump can supply all for S/G’s

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Auto starts for MDAFW pumps (2 & 3)?

A
  • SI (18/26 delay), overrides all other starts
  • Lo-Lo Ls/g(15%) 2/3, 1/4 S/G (time delay)
  • AMSAC. (No delay)
  • MFW pumps Trip (No delay)
  • Diesel (xfr->dsl)(14 delay), overrides 0 delay starts
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Trips for MDAFW pumps

A

O.C.

Load shed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What steam traps must be in service for terry turbine to be operable?

A
  • Traps on supply lines (104,105,106)
  • Traps off bypass lines of MSIV leads 2 & 3
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Describe FCV-95 Auto open signal Trips

(auto starts to TDAFW)

A

Steam supply isolation valve to terry turbine dc powered, panel SD-12

  • Lo-Lo Ls/g < 15% 2/3, 2/4 S/G’s
  • UV (12 kv bus) 1/2 relays, 2/2 buses
  • AMSAC -o.c.

-loss control power, ovrld relay (SI blocks ovrld relay) These Trip bkr for valve=> valve fails as is (not shut)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Describe Control scheme for TDAFW LCV’s?

MDAFW LCV’s?

A

TDAFW valves (ac)

  • no control scheme Electro hydraulic operated valves

MDAFW valves (ac)

  • median selected Ls/g setpoint
  • runout protection, Max valve position based on discharge pressure (1065# = valve must be full closed, ramps up to 1203# where there is no limit, 100% open)
  • valve position takes lowest of two
  • valve doesn’t get power unless pump bkr closed Or
  • valve “cut in”
  • if no power valve fails open
  • manual tracks auto, if in man when pump is off, pump inoperable b/c auto demand=0 => man demand = 0
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the AFW dedicated volume in the CST?

Are units the same?

why or why not?

A

U-1 51%(200,000 gal)

U-2 43%(166,000 gal)

U-2 has cold head design => it will take less time to bring unit from HSBY->RHR => lesswater

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Trips for TDAFW pump

A

Overspeed Trip throttle valve will shut (FCV-152) on mech overspeed via spring force.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Purpose of governor valve for TDAFW pump

A

FCV-15 maintains 4150-4200 rpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is power supply to TDAFW pump LCV’s? Why?

A

480v bus G

Each AFW pump has its own bus/train

TDAFW = G

all LCV AFW pump 2 = H

all LCV AFW pump 3 = F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Describe purpose of AFW check valve leak detection

A
  • Where AFW connects to MFW there is check valve on AFW side
  • Temp detector up stream of check valve
  • alarms if high temp MFW leaks past check valve
  • high temp water gets to AFW pumps, pumps could vapor lock when pump tries to start
  • AFW designed for CST water < 100 deg, MFW temp >400 deg
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How is minimum volume ensured on CST’s?

A

All suctions for loads other than AFW tap off of tank above point that ensures min vol maintained

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Purpose and design of AFW

A
  • source of FW when MFW unavailable
  • safety related means remove decay heat
  • c/d RCS to < 350 deg
  • TDAFW 870 gpm, 50 recirc, 205/ SG
  • MDAFW 460 gpm, 50 recirc, 205/ SG../ pump
How well did you know this?
1
Not at all
2
3
4
5
Perfectly