Sequence of opening steam supplies to MFP?
LP gov valves open first (hot reheat), not enough steam pressure to operate pump => HP gov valves open (MSS). When (hot reheat) LP has enough steam pressure, the HP will close down. At 100% power, HP closed, MFP operating off LP only
What is FCV-420
Interlocks
Mainfeedwater long recirc valve
Discharge #1 fw htrs -> MN condenser
Used for chemistry cleanup of fw
If any FW htr outlet > 320 deg valve will shut (won’t open) to protect MN cond from water hammer
What gives FWI signal?
SI P-14 (Ls/g > 90% NR) - turbine Trip - MFP Trip - FWIV's - FRV and Byp
P-4 w/ Tave < 554
- FRV and Byp
How do you reset FWI signal (3)
Reset SI
Cycle RTB
Reset FWI
Precautions and limitations for MFW (3)
- ensure > 2% Rx power before roll MFP
- ensure fw cut into fw htr before extraction stm
- any perturbation in condensate will affect MFP, FRV, Ls/g
How are MFP protected from overheating during low flow conditions?
FCV-53 and 54 open to provide minimum recirc to condenser of 1000 gpm
Pump running for recirc valve to open (>60 d/p)
Steam sources to #1FWHtrs (3)
-HP turbine 3rd stage extraction
-MSR HP drain tank
-MSR excess steam vent
What happens to FWH #1 on a hi hi level (2)
-Trip closed MSR HP drain tank drips
-vent air supply to non-return valves from 3rd stage HP ext steam
What actions happen if Hi level in #2HDT(1)
Trips closed the drips valve from the #1FWHTR
What are the MFW Reg Valves and purpose(3)
FCV-510/520/530/540
-control S/G level via the DFWCS>30% power
-isolates on a FWI
-manual operation: reverse acting valve
What are the MFW Reg bypass valves and purpose?(3)
-FCV-1510/1520/1530/1540
-controls S/G level via the DFWCS<30% power
-isolates on a FWI
-no manual operation
What are the MFW isolation valves and purposes?
FCV-438/439/440/441
-isolates on a FWI