Electrical flow path from PMG to isophase buses
PMG(spins, induce voltage) PMG stator(3 phase ac) FCB voltage regulator (ac->dc) AC exciter stator(stationary mag field) AC exciter rotor (3 phase ac) Fuse wheel (diodes ac->dc) Gen rotor (rotating mag field) Gen stator (induced 3 phase ac) Isophase buses
What does a high RF monitor reading mean?
What does a high Gen Condition monitor reading mean?
1-High RF, high GCM
2-High RF, low GCM
RF- arching is occurring
GCM- no degraded insulation in gen
1-arching outside gen
2-arching inside gen
How can you verify a valid low GCM reading?
Place filter in service, if reading rises=> valid reading (filtering out insulation degradation)
What does the supplementary excitation (power system stabilizer) do?
Minimize the effects of grid transients on Generator by making AVR goes with transient not fight it.
How does exciter ground detector work?
Once /24 hrs for one minute brushes contact slip rings on exciter, detect for grounds on exciter and Generator rotor
-100vdc placed on exciter, if no ground alarm circuit is not completed=> no alarm
How is main Generator cooled?
H2 gas and stator core cooling water
Stator water flows through 1/3 of stator coils
H2 gas cools rotor and Generator core
Both H2 gas and stator water is condensate cooled
Difference between U-1 and U-2 generators?
U-1. Axially cooled
U-2. Zone cooled
What interlocks take effect when Field Circuit Breaker is closed?
- MOD is prevented from operation
- 24 hr ground detector timer starts
- AVR and MVR able to adjust from no load position
- exciter cooling starts
- MBT cooling oil fans start
- ISO-phase bus duct cooling starts
What interlocks must be met to close field circuit breaker?
- MOD must be fully closed or fully open
- isophase ground switch must be open(not grounded)
What must be met to open exciter field breaker?
Both Generator output breakers must be open
What will place AVR to manual on main Generator ?
Excessive V/Hz
Loss of sensing inputs
Over-excitation
What actions happen on Unit Trip (per lockout relays 86G1 and 86G11
Turbine Trip Aux xfr feeders Trip Auto xfr to S/u 500 kv Generator bkrs Trip Exciter field bkr Trip Trip #2 htr drn pump If aligned to degraded 230 kv - Trip cond bstr running in auto - prevent any auto start of cond bstr pump
What will happen if MW transducer fails?
MW feedback out
Programmed ramps disabled
LDA disabled
What are the Generator output breaker Trip relays?
Backup Out of step Negative sequence Under frequency Special protection