Pzr, Press & Lvl Flashcards
Safety limit
Safety lift set point
PORV lift set point
PORV close interlock
2735 psig
2485 psig
2335 psig
2185 psig
Hi Press. Rx Trip
Lo Press Rx Trip
P-11
Lo Press SI
2385 psig
1950 psig
1915 psig
1850 psig
Spray full open/ hi Press alarm
Spray start open
Prop htrs full off
NOP (prop htrs 50% on)
Prop htrs full on
B/U htrs on
2310 psig
2260 psig
2250 psig
2235 psig
2220 psig
2210 psig
LTOP permissives before cutin will work on PORV
PCV455 C
RCS cL loop 3 (TE-433b) < 283 deg
RCS hL loop 4 (PT-403A) > 435 psig
Which PORV’s have emergency close feature from HSDP?
All of them
Which PORV’s are class 1?
What features do these have only?
PCV-455c and 456
LTOP cut in, N2 back up, controlled by own channel
What PORV not class 1?
How is this PORV different?
PCV-474
No LTOP, no N2 b/u, controlling channel is second highest via Press controller 455k
Can open by running demand up manually on 455k
Describe Lpzr Control bands?
What happens at +/- 5% Lpzr from program?
What happens at Lpzr < 17%
Lpzr ramped from 22-60 % from
0-100% based on auctioneered hi Tave (547-577)
+ 5% = alarm, b/u htrs on
- 5% = alarm
< 17% letdown isolation (oriface vlves, 459/460)
Describe Pzr htrs include power supplies?
1 - proportional htrs, p.s. 13D
2 - b/u p.s. 13D (1G)
3 - b/u p.s. 13E (1H)
4 - b/u p.s. 13E
What Pzr htrs are able to powered at HSDP?
What interlocks are still active from HSDP?
Htrs 2 & 4
All interlocks disabled excepted for Lpzr < 17% trip
Auto trips on Pzr htrs
All off
Lpzr < 17%
Prop
SCR cabinet low cooling flow
Over current
Describe b/u htrs when power from vital b/u?
Indicating lights not on (de-energized on swap)
No interlocks work (off on SI, load shed)
Use kw amps for indication
1G
1H
Describe htrs on loss of non-vital power?
- loss of heaters, non-vital p.s.
- indicating lights still indicate bkr closed(D.C. Control power) false indication
What valve is primarily controlled by Lpzr Control?
What other inputs feed into this valve?
FCV-128
FE-128 inputs a feedback signal, so Lpzr cntrl sends a demand and the flow instrument lets valve know how he is doing
What happens if FT-128 fails high?
FCV will close because it thinks flow is too high
- lose seal injection
- actual Lpzr will go down