What is preferred source of power during outage?
Back feeding via 500 kv switchyard, so auto transfer is still available
U-1 main gen output breakers
U-2 MG output breakers
230 output bkr
632, 532
642, 542
212
Purpose of 230 kv switch yard?
Purpose of 500 kv switch yard?
230- power during S/u, S/d, provide immediate source of offsite power during unit trip
500- connect MG to grid, provide delayed access source of offsite power
What allows us to backfeed from 500 kv switchyard and not motor the MG?
MOD (motor operated disconnect)
Numbering scheme of transformers
1-1………. first number unit, second number voltage…=>. Aux xfr 1-1 , unit 1, step down from 25 kv -> 12 kv
Aux xfmr 2-2, unit 2, step down 25 kv -> 4 kv
Describe vital and nv bus numbering
12 kv D,E nv
4 kv D,E nv
4 kv F, G, H vital (diesel backed)
Difference between vital and nv 480 bus configuration
Vital- ever bus has dedicated 4 kv -> 480 v step down xfmr
NV- ten step down xfmr’s going to 17 480 v buses with cross tie bkrs for flexibility