Digital Radiation Monitoring System Flashcards

1
Q

What Rad monitors are part of the Digital Radiation Monitoring System?

A
  • Plant Vent (RM-14, 24, 28, 87) and “” R
  • SJAE (RM-15) and ““R
  • CNMT exh (RM-44 A & B)
  • Plant Vent Gross (RM-29)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What will be displayed if a DRMS RDU or LRP overranges?

What will be displayed if an RDU loses comunicaton with and LRP?

A

overrange - E.EEE+EE

loss communication - E009

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What will be displayed on an RDU or LRP if detector counts less than setpoint (for 60 sec)?

A

the FAIL/ ACK light will illuminate and an alarm will sound

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What will happen on a Hi-Rad on RM-29 (plant vent gross)

A

Audible alarm

alarm sent to sacramento (California Office of Emergency Services)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When would you “bypass” RM-44A and B

A
  • RM-44 A and B actuate CVI
  • energize to actuate
  1. loss of power (maintenance)
  2. if restore power, elect noise could actuate CVI
  3. before restore power take CVI to bypass
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Amber light

A

Alert measured parameter has exceeded the alert set point

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Red indication light

A

High - measured parameter has exceeded the high set point

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Green indication light

A

Fail- low detector counts less than setpoint for 60 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Blue indication light

A

Test- module is being tested by : check source , selected by Cal or test, test/norm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

White local indication

A

At RDU, control mode key switch on the LRP is in the Local position

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

White normal

A

Indicates monitor is operating normally with sample flow , no alarms, no test & no purge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly