25 kV Electrical System Flashcards

1
Q

Why is the output of the Generator split into its 3 individual phases?

A

Output is relatively low so current is very high (30,000 amps)( high heat )

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How is iso phase bus cooled? What are auto features of the cooling system?

A

Hollow conductor, air flow through middle and opposite direction on outside of conductor between guard pipe (cooled by SCW) Auto start of stby fan - loss running fan (in on position) - hi ISO phase bus temp 155 deg - other fan off and 25 kv energized - exc field bkr closed - one output bkr closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What interlocks must be met to operate the MOD?

A
  • mn gen UV relay actuated - exciter field breaker open - both output breakers open - all aux xfr feeder breakers open - 25 kV ground switch open
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What interlocks prevent energizing a grounded 25 kV system? (Can’t close ISO phase bus ground switch)

A
  • MOD must be fully open
  • exciter field breaker must be open (FCB)
  • aux xfr feeder breakers open
  • output breakers open (PCB)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the danger of manually isolating a sudden pressure relay on 25 kv XFMR? When should isophase bus blower be in service, other than normal ops (generator carrying load on grid)?

A
  • w/unit trip cutin……may result in Unit Trip (normal ops slow transient, catasrophic failure=> rapid press rise - if available isophase bus blower should be in service when back feeding from 500 kV
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Describe U-1 Main XFMR (25->500 kv)

A
  • head tank - contains oil, maintains pressure inside xfmr, small amount air in air bladder
  • radiator - six systems, each has (1 pump, 1 hx, 4 fans), fans pull air through hx cooling oil, pump moves oil
  • oil - electrical insulator and cooling medium
  • gas detector - oil breaks down or winding insulation breaks down, creates H2

half of cooling systems start when xfmr energized, other half start on high oil temp

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Describe U-2 main XFMR (25->500 kv)

A
  • head tank - contains oil, maintains pressure inside xfmr, small amount air in air bladder
  • radiator - 3 systems, each has (1 pump, 1 hx, 3 fans), fans pull air through hx cooling oil, pump moves oil
  • oil - electrical insulator and cooling medium
  • gas detector - oil breaks down or winding insulation breaks down, creates H2

sequential starting of cooling systems: (3 possible seq)

  • 1st group start when xfmr energized
  • 2nd group start on oil temp of 50 /65 hot spot
  • 3rd group start on oil temp of 70 /85 hot spot
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Describe Aux XFMR 1-2 (25->4 kv)

A
  • XFM shell - kept at positive pressure N2
  • radiator - 2 systems, each has (2 hx, 6 fans), fans pull air through hx cooling oil, natural circ moves oil
  • oil - electrical insulator and cooling medium

half of cooling systems start hot spot therm 80

other half start hot spot therm 85

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Describe Aux XFMR 1-1 (25->12 kv)

A
  • XFM shell - kept at positive pressure N2
  • radiator - 10hx, 16 fans pull air through hx cooling oil
  • oil - electrical insulator and cooling medium, circulated by natrual circ and pump
  • oil pump - starts when second group fans start

1st group cooling - 12 fans starts 80 ºC

2nd group cooling - 4 fans and pump 85 ºC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

what are the protection relays for the following XFMR’s

Main XFMR (25->500 kv)

Aux XFMR 1-1 (25->12 kv)

Aux XFMR 1-2 (25->4 kv)

A

Main:

  • o.c. (open PCB’s)
  • over voltage open (open PCB’s)
  • line directional o.c. phase (open PCB’s)
  • line directional o.c. ground (open PCB’s)
  • line pilot wire diff (open PCB’s)
  • sudden pressure (unit trip)

1-1

  • o.c. (unit trip)
  • sudden pressure (unit trip)
  • diff (unit trip)

1-2

  • x-winding ground o.c. (alarm)
  • y-winding groud o.c. (alarm)
  • sudden pressure (unit trip)
  • diff (unit trip)
  • o.c. (unit trip)
  • lockout (unit trip)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The ground switch must be open to do what?

A

Close FCB
Close aux transformer feeder breakers
Close 500kv PCBs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The MOD must be fully open to close what?

A

The ground switch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the Sudden pressure relay and what will it cause?

A

A catastrophic fault will result in a rapid pressure rise

Causes a unit trip
-Trips turbine
-Opens 500kv
-opens FCB
-opens aux feeder breakers
-transfers to startup

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What kind of windings are on the 25kv, 500kv

A

25kv are the primary windings (DELTA)
500kv are the secondary windings (WYE)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the hydran monitor monitoring and what is considered a bad value?

A

It is looking for gases that are formed due to oil breakdown and insulation breakdown

High numbers are bad

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What are the p/s for the cooling groups on the Unit 1 MBTs? What happens if power is lost?

A

Group 1=11D
Group 2=11E

If power is lost to either bus, it will result in loss of half of the cooling capability, but not a complete loss.

17
Q

How are the Unit 1 MBTs alarms detected? How does reflash work?

A

It will alarm in the CR
Other alarms from same phase will reflash, but other alarms from other phases will be blocked
-this will require a 4hr como measure to check the other 2 phases

18
Q

Unit 2 fan and pump power supply. What happens if power is lost?

A

Power seeking power supply for all cooling fans and pumps. Automatically switches back to normal power supply when it returns

19
Q

How are the Unit 2 MBTs alarms detected? Reflash capabilities?

A

Alarms In the CR. Alarms on other phases will reflash if there is an alarm on 1 phase.

20
Q

What do the aux transformers have to keep the air out?

A

Have N2 to keep air out.

21
Q

Aux Transformers #1 25kv to 12kv cooling and auto starts

A

2 banks of cooling with an auto start of bank 1 @80degC and bank 2 @85degC

22
Q

Aux transformers 1 protections and actions?

A

-sudden pressure relay-> unit trip
-differential->unit trip
-overcurrent->unit trip
-ground overcurrent (no auto trips) alarm only

23
Q

Aux trans #2 cooling?

A

Natural circulation

24
Q

How many secondary windings does the #2 aux trans have and why?

A

2 secondary
The Y windings only serve the 4kv bus E due to two condensate/ booster pump sets and the heater drain tank pump (equal to 11,500hp) the X winding powers 4kv busses D,F,G, and H

25
Q

Aux transformer #2 protection relay and actuations

A

Overcurrent ->unit trip
Differential-> unit trip
Sudden pressure -> unit trip

26
Q

Why should the isophase cooling be kept on while back feeding?

A

To help prevent accumulation of debris in ducting

27
Q

What must you do if you get a high temperature alarm in a MBT?

A

It must be locally reset