Fire Water System Flashcards
How does a deluge system work in the Fire Water System?
- The water pressure that will go through deluge valve will hold the deluge valve shut at the valve operator
- to activate the system the pressure must be bled off and the deluge valve will open
What will actuate the fire water pumps 0-3 and 0-4?
What will actuate the fire water pumps 0-1 and 0-2?
- fire water pressure drops below 140 psig with time delay
- .15 sec 0-3
- 5 sec 0-4
- fire water pressure drops below 75 psig with time delay
.15 sec 0-1
5 sec 0-2
What happens in 15 mimutes after you get a fire detection alarm if you cant prove there is no fire?
site must declare a Unusual Event
what components does deluge system protect?
What are the different methods to actuate a deluge system?
- Seal oil skid
- xfmrs
- MFPs
- turbine brngs 2-9
- energize electromagnet bypass valve
- local manual drain valve (xfm only)
- heat actuated device
- close pilot valve, open bell test valve
What subsystems exist in fire water system?
What do those subsystems protect?
what is source of water to those subsystems?
Plant Yard Loop
- around main power block
- plant interior loop
- Raw wtr resv
- patton flats
- interior loop
Plant Interior system
- inside power block (seismic qual)
- b/u cooling CCP
- yard loop (Raw)
- FWST (pmp 0-1 , 0-2)
- ASW/Cond via dies pmps
Patton Flats
- outside power block
- b/u for Plant yard loop
- FWST 0-2 (FWP 0-3, 0-4)
What are the jockey pumps (0-1 and 0-2) supplying water to?
Which fire water pumps have feature to lock in contacts and prevent tripping due to electrical logic?
to patton flats (South site fire water system) maintaining pressure ~ 150 psig to prevent cycling of pumps 0-3 and 0-4
FWP 0-1 and 0-2