Turbine Building Chilled Water - 1.0 Flashcards

1
Q

What are the CW pump interlocks?

A
  • Trip on low flow ≤1100 gpm. Bypassed for the first 20 secs after pump start.
  • Auto start on low flow of running pump.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What do the different bezel light indications mean?

A
  • Solid light: High flow.
  • Flashing: Low flow.

*Hi/Lo flow bezel illuminates solid on high flow, flashes on low flow.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the TB chill water loads?

A
  • DW unit coolers(8).
  • RBVS supply unit coolers.
  • Steam tunnel coolers.
  • PCP/SCP room coolers.
  • Recirc pump Motor air coolers.
  • FWH room coolers.
  • TB supply unit coolers.
  • RWS/SRW
  • SAS
  • MVP Seal cooler
  • CRD Unit coolers
  • Process sample cooler.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When do the containment isolation valves close?

A
  1. -129”
  2. 1.68#
  3. Associated CS Logic PB Depressed:
    -Channel ‘C’(‘D’) – Closes ‘B’s’(‘A’s’) Inbd(Outbd)*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What happens to DW cooling on a LOP?

A

RACS swaps over to DW cooling.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the Chiller trips?

A

Compressor Bearing High Oil Temp*
Compressor High Refrigerant Temp*
Compressor Impeller Displacement*
Compressor Low Oil Pressure
Compressor Low Oil Temp*
Compressor Motor & Oil Pump Motor Overload
Evaporator Low Refrigerant Pressure*
Evaporator Low CW Flow
Evaporator Low CW Temperature (40F) (Load Recycle)
Condenser High Refrigerant Pressure*
Condenser Hi-Hi Refrigerant Pressure

*Safety Circuit Complete (white) illuminated when w/in specs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the Chill water pump trips>

A

U/V, O/C
Low Flow (1100 gpm, 20 Sec TD)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How does the Motor Restart Delay/Load Recycle work?

A

Motor Restart Delay/Load Recycle Differs from 1E/CR Chillers
1. When a chiller starts, the motor reset delay timer prevents restart for a period of 15 minutes.
2. The only exception to this is the Load Recycle:
* Chiller trips on low discharge CW temp, auto restart when CW temp ≥ 50F.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What happens to TB chill water during a LOP?

A

LOP Summary:

  1. The Chillers and circ pumps trip.
  2. The HV-9530A1, A3, B1, B3 valves close @ T-13 seconds (Chill water supply isolates)
  3. Both RACS pumps get a start signal @ 85 seconds
  4. The HV-9530A2, A4, B2, B4 open @ T-85 seconds to (RACS Supply to DW
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What happens to TB Chill Water during a LOCA?

A

LOCA Summary:

  1. Chillers trip on loss of TACS (condenser high refrigerant pressure).
  2. The primary containment isolation valves (HV-9531A1-A4, B1-B4) auto close and isolate the DW loads.
  3. System is unavailable until the LOCA signal clears.
  4. RACS will load shed and not be able to supply cooling to DW loads (can be manually overridden if required)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What happens to the containment isolation valves when either OPEN RACS/CHW are depressed?

A
  1. Both Sets of CW supply/return valves will auto close when their respective loop RACS supply/return valves “OPEN RACS” control switch is depressed.
  2. Both sets of RACS supply/return valves will auto close when their respective loop Chilled water supply/return valves “OPEN CHW” control switch is depressed.