What indications can an operator use to verify SLC system operation?

A
  1. Start PBs backlit red
  2. Squib Valve continuity extinguished and annunciator alarms
  3. SLC pump discharge pressure slightly > Reactor pressure
  4. SLC tank level decreasing
  5. APRM level decreasing
  6. Ensure RWCU isolation
  7. CS Line Break Alarm
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the purpose of SLC?

A

To S/D the Rx from highest power without CRDs.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

List the power supplies for the SLC pumps.

A

A - 10B212
B - 10B222

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

SQUIB Valve power supply.

A

SQUIB valves are powered from the motor buckets.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is T/S requirement for SLC pump flow rate?

A

41.2 GPM per pump.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

When do the pumps trip?

A

They trip when both level transmitters sense 325 gal remaining in the tank. (Bypassed when in test or loss of DC to RRCS Panel.)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

SLC Flowpath.

A

SLC Tank > 2 50% capacity pumps > 2 150% capacity SQUIB valves > Into ‘A’ CS Loop.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the function of the heat trace?

A

To keep the pump heads and suction lines warm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What are the heater ratings and Power supplies?

A

40KW mixing, 282 MCC
10KW operating 252 MCC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What indications do you have if a SLC pump fails to start?

A

RRCS Initiation Failure alarm illuminates 30 seconds after pump fails to start

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What operational difference is possible when operating SLC at the local control panels that is not possible remotely?

A

Operation of either local switch will START only the associated pump and will not FIRE either of the squib valves, or cause a RWCU system isolation.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the TS Temperature limit associated with the SLC tank?

A

Temperature of the solution in the storage tank must be > 70oF as per Technical Specifications (prevents precipitation of sodium pentaborate)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What automatic actuations are associated with the SLC pumps?

A
  1. RRCS - Auto start
  2. SLC low level(approximately 325 gallons gross or instrument zero) - Auto stop
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the SLC tank low level alarm?

A

4640 gallons net

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the TS flow limit associated with the SLC pumps?

A

41.2 gpm minimum

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What are the pump start conditions?

A
  • RPV level -38”,
    OR
  • RPV pressure 1071#,
    OR
  • Manual,
    AND
  • APRM power >4%
    OR
  • APRM INOP ≥ 230 secs
17
Q

SLC pumps and RWCU isolation valves relationship.

A
  • ‘A’ pump shuts F001
  • ‘B’ pump shuts F004
18
Q

Why is moderator temp important to the SLCS?

A

Higher moderator temp requires less Boron concentration.

19
Q

Why is a proper valve lineup important?

A

Proper valve L/U prevents SLC dilution and air binding.

20
Q

Differences of pump operation from control room or local panel.

A

Running from local panel does not initiate SQUIB valves.

21
Q

What happens if SLC stops with RACS init. present?

A

SLC MAN OHA comes in.

22
Q

What happens when RRCS fails to initiate?

A

If it fails to initiate, OHA will come in 30 secs after it should have started.

23
Q

What is Cold Shutdown Boron Weight?

A

The weight of soluble boron required for injection to place the reactor in a cold (70°F) shutdown condition, at the most reactive time in core life. This is assumed to have been injected when there is 1100 gallons, (net), of solution left in the SLC tank.