Retainment Overrides Flashcards
Reactor power is > 24% AND Steady-State FLFWTR > 1.00 *
INITIATE Corrective Action within
15 minutes.
RESTORE Feedwater temperature to the
analyzed region within 2 hours
OR REDUCE RTP to less than 24% of
RATED THERMAL POWER.
WITHIN the next 4 hours
Failure of Main Turbine to runback on
a Loss of Stator Water Cooling for
more than 15 seconds.
REDUCE Recirc Pump speed to MINIMUM.
LOCK the Mode Switch in SHUTDOWN.
Loss of Stator Cooling
for > 2 min.
AND Reactor Power > 18% **
REDUCE Recirc. Pump speed to MINIMUM.
LOCK the Mode Switch in SHUTDOWN.
II.C TRIP the Main Turbine.
Bearing 1–10 Vibration ≥ 11 mils @
1800 RPM *
Bearing 11–12 Vibration ≥ 7 mils @
1800 RPM *
IF Reactor Power is ≥18%**
THEN PERFORM the following:
REDUCE Recirc. Pump speed to MINIMUM.
LOCK the Mode Switch in SHUTDOWN.
IMMEDIATELY TRIP the Main Turbine.
EHC Pressure ≤1200 psig
AND Lowering (multiple indications)
AND EHC is required to maintain the
Main Condenser as a heat sink.
IF the Reactor is not shutdown,
THEN LOCK the Mode Switch in
Shutdown.
Steam Tunnel Cooler Inlet
Temperature (A2541) OR any
TWO channels of Main Steam
Tunnel Temperature NUMAC
readings are rising AND
expected to exceed 155°F.
REDUCE Recirc. Pump speed to
MINIMUM.
LOCK the Mode Switch in SHUTDOWN.
Steam Tunnel Temperature
>145ºF at CRIDS point A2541
REDUCE Recirc. Pump speed to
MINIMUM.
LOCK the Mode Switch in SHUTDOWN.
Any unanticipated Main Steam
Tunnel Damper closure as a
result of increased room
temperature with indication of a
break from a High Energy
system
REDUCE Recirc. Pump speed to
MINIMUM.
LOCK the Mode Switch in SHUTDOWN.
Reactor Power reduction cannot restore
and maintain condenser pressure < 6.5”
HgA
REDUCE Recirc. Pump speed to MINIMUM.
LOCK the Mode Switch in SHUTDOWN.
Turbine Load <30%,
AND
Condenser Pressure > 5.0” HgA.
IF Reactor Power is ≥18% *
THEN PERFORM the following:
REDUCE Recirc. Pump speed to MINIMUM.
LOCK the Mode Switch in SHUTDOWN.
TRIP the Main Turbine. [CD-896E]
Total Loss of Circ Water
AND the Main Condenser is being used
as a Heat Sink.
IF the Reactor is not shutdown,
THEN:
REDUCE Recirc. Pump speed to MINIMUM.
LOCK the Mode Switch in SHUTDOWN.
CLOSE all MSIV’s
AND Steam Line Drains
1-KA-HV-7595 is CLOSED
AND
Instrument Air Header Pressure
≤ 70 psig. (PI-7603A(B) or A3016)
AND
Instrument Air Header Pressure
continues to Lowe
IF the Reactor is not shutdown,
THEN:
REDUCE Recirc. Pump speed to
MINIMUM
LOCK the Mode Switch in
SHUTDOWN.
Instrument Gas Pressure ≤ 70 psig
CLOSE Instrument Air Shutoff Valve
KLHV-5125
IF Instrument Air was cross-tied in
Operator Action Step A.4.a.
Instrument Gas Pressure ≤ 50 psig
REDUCE Recirc. Pump Speed to
MINIMUM.
LOCK the Mode Switch in SHUTDOWN.
PLACE RCIC and/or HPCI in service to
control Reactor Pressure and Level.
CLOSE the Inboard MSIVs.
CLOSE the following:
● HV-5124A
● HV-5124B
Drywell Pressure is ≥ 1.5 psig
and rising.
REDUCE Recirc. Pump Speed to
MINIMUM.
LOCK the Mode Switch in Shutdown.