RBVS Flashcards

1
Q

What is the purpose of RBVS and how does it accomplish this?

A

Maintains dP to minimize ground level release, not necessarily for accident conditions i.e. 10 CFR 100
Provides negative dP to ensure leakage is always into the building.
RBVS provides a complete exchange of 1 volume of Rx building air per hour

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Where are the RBVS room coolers located?

A

Room Coolers (2 per room)
1. HPCI, RCIC, RHR, Cores Spray (all cooled
by SACS)
2. SACS Room (Cooled by Control Room
Chilled Water AP400/BP400)
3. Steam tunnels (normally cooled by
chilled water, can be cross tied to RACS)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What do the RBVS duct heaters keep the various room temperatures at?

A
  1. Maintain HPCI and RCIC rooms >60F
  2. Maintain SLC room temp >70F
  3. Maintain Rx Building >40F
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

how does the RBVS fan trips/isolations remove power and how is power resored?

A

RBVS fans trip and dampers isolate (trips the 1E breaker [in the field] which indirectly feeds the RBVS supply and exhaust fans, must be locally reset AND started at breakers [1E swgr pistol grip switches])

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the RBVS fan trip and damper isolation setpoints?

A
  • Drywell pressure (1.68psig)
  • RPV Level 2 (-38”)
  • Rx Building Hi Rad (1X10-3uci/cc)
  • Refuel Floor Hi Rad (2X10-3uci/cc)
  • Lo Flow (<30,000scfm w/ 90sec TD – by say, outlet damper closure)
  • Non 1E Breaker trips on undervoltage.
  • These are PCIS NOT NSSS isolations ONLY
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What prerequisites must be met before re-shutting a tripped RBVS 1E Breaker?

A

To reclose the 1E breaker, all initiating signals must be clear and
PCIS reset; then, the breaker must be manually reclosed at the
480V USS. (Top breakers on 10C650)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Describe RBVS and RBVE fan auto start operations and interlocks.

A
  • Low flow (<30000scfm for 90seconds)
  • Two exhaust fans must be running to start a supply fan (if at any
    time < two exhaust fans are running, all supply fans trip).
    * This trip looks at the non-1E
    breaker position => when
    the 1E breaker trips, the non-1E
    breaker will trip on U/V.
  • LOP sequencer will start all RBVS & RBVE fans in RUN 19
    seconds after the event (The RBVS fans will actually start
    6 seconds after the RBVE fans start).
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When do the RBVS steam leak dampers close?

A

Close on room high temperatures

How well did you know this?
1
Not at all
2
3
4
5
Perfectly