Immediate Operator Actions - .5 Flashcards

1
Q

Bearing 1–10 Vibration ≥ 12 mils
@ 1800 RPM
Bearing 11–12 Vibration ≥ 8 mils
@ 1800 RPM

A

IF Reactor Power is ≥18% **
THEN LOCK the Mode Switch in Shutdown.

IMMEDIATELY TRIP the Main Turbine.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

In service EHC Pump tripped.

A

START the standby EHC Pump.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Degraded Main Condenser Vacuum

A

REDUCE Reactor Power to maintain
MAIN CONDENSER A(B,C) VACUUM LO
Overhead Alarm Clear

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Trip of the Inservice Service Air
Compressor

A

PLACE the out of service Service Air
Compressor in service. (AB.ZZ-0001)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Primary Containment Isolation
Valve FAILS to automatically
ISOLATE following a valid
isolation signal.

A

PERFORM EITHER of the following:
● CLOSE a redundant isolation valve
● CLOSE the valve manually.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Irradiated fuel damage

A

SUSPEND the handling of Irradiated
Fuel/Components

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Significant loss of Fuel Pool
inventory.

A

PERFORM the following:
EVACUATE the Refuel Floor.
RETURN irradiated fuel assembly to the Vessel
or Pool.
LOWER any bundle in the Fuel Prep Machine
to the Full Down Position.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Multiple Control Rods are
Drifting Simultaneously.

A

LOCK the Mode Switch in SHUTDOWN.

(Drifting Does NOT include
Scrammed or Scramming Rods)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

ANY Neutron Monitor
UPSCALE/INOP.
(SRM, IRM, LPRM or APRM)

A

TERMINATE all Fuel Movement
AND Control Rod withdrawal.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Reactor Power is Rising.

A

REDUCE Reactor Power to Pre-Transient
value.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Dual Reactor Recirc Pump
runaway.

A

LOCK the Mode Switch in Shutdown.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Single Reactor Recirc Pump
runaway.

A

PRESS the MANUAL SPEED HOLD
Pushbutton for the affected Recirc Pump
Controller.

REDUCE the NON-affected Reactor Recirc
Pump Speed to Reduce Power to
Pre-Transient value

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Automatic Level control system
malfunction.

A

NOTE 1

As required,
MAINTAIN Reactor water level Manually
between LEVEL 4 and LEVEL 7.

REDUCE Reactor Power, as necessary, to
Maintain between LEVEL 4 and LEVEL 7.

**In manual, an operator, with no other responsibilities, should be assigned to maintain water level while the reactor is critical. **

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

RPV Pressure Rising

A

REDUCE Reactor Power to maintain
RPV PRESSURE HI Overhead Alarm Clear

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Uncontrolled Lowering of RPV
Pressure
AND the Reactor is not Shutdown.

A

LOCK the Mode Switch in Shutdown.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly