What temperature is the SSW pump rooms, MCCs and traveling screen motor rooms kept at?

A

> 60F(minimum design temperature)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Describe the SSW ventilation pump room supply fans operation.

A
  1. Run – Starts the supply fan and modulates the outside air, recirculation and exhaust dampers to maintain temperature and AUTO exhaust fan starts.
  2. Auto
    • 1st fan operates 82F – 74.5F
    • 2nd fan operates 99F – 91.5F
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Describe the SSW ventilation pump room exhaust fans operation.

A
  1. Run – starts fan
  2. Auto – Exhaust fan starts anytime associated supply fan starts.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When do the SSW ventilation supply and exhaust fans trip?

A

Supply and exhaust fans trip on low flow (20,100scfm / 20sec

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Describe the operations of the travelling screen room supply fans.

A
  1. Run – starts fan and controls dampers (62F closes outside damper and opens recirc)
  2. Stop – fan stops, outside damper closes, recirc damper opens.
  3. Auto – starts on low flow on running fan.
    • Normally one fan in Run and 1 in Auto. STBY fan starts on low flow on the running fan.