What temperature is the SSW pump rooms, MCCs and traveling screen motor rooms kept at?
A
> 60F(minimum design temperature)
2
Q
Describe the SSW ventilation pump room supply fans operation.
A
- Run – Starts the supply fan and modulates the outside air, recirculation and exhaust dampers to maintain temperature and AUTO exhaust fan starts.
- Auto
- 1st fan operates 82F – 74.5F
- 2nd fan operates 99F – 91.5F
3
Q
Describe the SSW ventilation pump room exhaust fans operation.
A
- Run – starts fan
- Auto – Exhaust fan starts anytime associated supply fan starts.
4
Q
When do the SSW ventilation supply and exhaust fans trip?
A
Supply and exhaust fans trip on low flow (20,100scfm / 20sec
5
Q
Describe the operations of the travelling screen room supply fans.
A
- Run – starts fan and controls dampers (62F closes outside damper and opens recirc)
- Stop – fan stops, outside damper closes, recirc damper opens.
- Auto – starts on low flow on running fan.
- Normally one fan in Run and 1 in Auto. STBY fan starts on low flow on the running fan.