What are the Circ water pump trips?
Motor Differential O/C
Bus O/C or Differential O/C
Discharge Valve Closed (20 sec TD)
What can cause a Circ water pump inop light?
No control power to breaker
Breaker in PTL
Breaker not in operate
Springs not charged
Loss of trip coil continuity
What logic is enforced when the Circ water stop enable light is in?
4 pumps running - to stop the 1st
pump its d/ch vlv must be closed to the mid position
≤ 3 pumps running - all running pump d/ch valves must be mid pos. AND stopped must be closed
What are the Recirc runbacks associated with the circ water system?
Intermediate (45%) – Loss of 1 CW pump (4 init) and vacuum > 4.5”HgA
Full (30%) – Loss of 1 CW pump (2 or 3 init) and vacuum > 5.8”HgA
What interlocks associated with the circ water start enable light are required to start the first circ water pump?
Control in MCR (NOT in Remote) and Discharge Valve 100% Closed
at least 2/6 pairs of condenser inlet and outlet valves must be fully open
NOTE: When starting the first CW pump there is a 20 second time delay between the pushing of the START PB and when the pump actually starts. This time delay allows the lube water storage tank to provide lubricating water and clear the lube water low flow interlock prior to the pump running.
What interlocks associated with the circ water start enable light are required to start the second circ water pump?
Control in MCR (NOT in Remote) and Discharge Valve 100% Closed
at least 3/6 pairs of condenser inlet and outlet valves must be fully open, AND the discharge valve of the running CW pump must be open to the MID position or more
What interlocks associated with the circ water start enable light are required to start the third/fourth circ water pump?
Control in MCR (NOT in Remote) and Discharge Valve 100% Closed
at least 3/6 pairs of condenser inlet and outlet valves must be fully open, AND the discharge valve of the running CW pumps must be open to the MID position or more, AND Cooling Tower Bypass Valve HV-2173 must be fully closed.
What occurs on an emergency trip of a CW pump?
PB control will trip the CW pump irrespective of the pump stop permissive signals. The discharge valve on the tripped pump will fully close and ALL running CW pump discharge valves will close to the MID position.
IF a single CW pump is running when the EMERG TRIP PB is depressed, the pump will trip and the discharge valve will fail as is.
What are the power supplies to the CW pumps and their discharge valves?
10A501 - A/C pumps
10A502 - B/D pumps
10A502->10B502 - A/C discharge valves
10A501->10A503 - B/D discharge valves
Can you open a circ water discharge valve without meeting the interlocks?
Yes, if the OPEN INTLK OVRD/RESET is pressed as well
What is the logic associated with stopping a circ water pump?
To stop the first pump when four pumps are running, the associated pump discharge valve must be closed to the MID position.
To stop a pump when < 4 pumps are running, ALL running CW pump discharge valves must be closed to the MID position AND the discharge valve of ALL stopped CW pumps must be fully closed.
Once the logic is met to stop a circ water pump, what are you indications and what actions must you take?
The ENABLE light will be lit and by depressing the stop pushbutton the discharge valve will fully close and the associated pump will trip
How do the cooling tower bypass valves operate when depressing the open pushbutton?
This PB opens the Cooling Tower Bypass Valve when control is not in REMOTE and
<2 CW pumps are running.
Under what conditions can the CT basin makeup valves be closed?
EITHER Makeup to River or Makeup to Intake structure vavles must be fully open to permit the CT basin makeup valve to be closed
Under what conditions will the Turbine Building CW sump pumps trip?
trips/isolate on high rad