NUMAC Leak Detection - 1.0 Flashcards
1
Q
Which systems are monitored by NUMAC and what causes isolations?
A
Nuclear Measurement Analysis and Control
1. MSIV Closure – 160F Main Steam Tunnel Temp
2. RHR (hi temp alarms only), RWCU (temps & diff flow), RCIC (temps & diff temps), and HPCI (temps & diff temps) isolations described in individual notes.
2
Q
What are the power supplies for the NUMACs?
A
- 10C620 (HPCI) – 1AJ481 (Lower Relay Room)
- 10C621 (RCIC)– 1BJ481 (Lower Relay Room)
- 10C640 (RCIC)– 1DJ481 (Lower Relay Room)
- 10C641 (HPCI)– 1CJ481 (Lower Relay Room)
- 10C609 – ‘A’ RPS bus (Back of MCR)
- 10C611 – ‘B’ RPS bus (Back of MCR)
3
Q
Where are the NUMACs located?
A
- HPCI/RCIC/RHR in LRR
- MSIV/RWCU in back of MCR.
4
Q
What happens when a flow element erodes?
A
If a flow element erodes, it will actuate at a higher gpm.