Aux Boiler - 1.0 Flashcards
What are the relief valve setpoints?
- # 1 @ 220 psig (Close @ 182 psig)
- # 2 @ 210 psig (Close @ 198 psig)
What are the 10C651 indications for the aux boiler monitoring?
In-service and out of service lights on 10C651 are indication of force draft fan breaker position.
When do the Fuel oil transfer pumps trip?
They trip on a day tank high level or million gallon tank low level.
What system can cause a boiler to trip?
Loss of service air.
How is the standby boiler kept warm?
With heating coils that use steam from the running boiler.
Function of the STBY 2 switch.
- Fuel oil pump starts on low pressure (130psig) and runs for 30 minutes after signal clears.
- Feed pump starts on low pressure (135psig) and runs for 30 minutes after signal clears.
What are the conditions that cause a boiler trip?
High Drum Pressure (200#)
High Furnace Pressure (-16”H20)
Low Combustion Air Press (-11.5’H20)
Low Atomizing Air Pressure (88#)
Low INST Air Pressure (60#)
Low Atomizing Media to F/O D/P (3#)
Low Oil Pressure (75#)
Lo-Lo Primary Drum Level (5” <norm)
Lo-Lo Aux Drum Level (5.5” <norm)
Loss of Power
FD Fan Motor Trip
Guns Uncoupled
Burner Trip
What are the loads that the boiler supplies steam to?
- Plant Heating
Heating Units
N2 Vaporizer
Domestic Hot Water
CST
RW - Offgas Recombiners Preheater
- HPCI/RCIC Testing
- Sealing Steam
- SJAE
- Condenser Heating & Dearator