How much does the EHC reservoir hold?
800 gal
What is the setpoint for the EHC relief valves?
2000#
What is the normal system pressure for EHC?
1600#
At what pressure does the standby EHC pump start?
1300#
At what EHC system pressure will the turbine trip?
1100#
List the power supplies for the EHC pumps?
‘A’ - 10B112
‘B’ - 10B141
What happens when EHC pump strainer is dirty?
Internal bypass opens.
List the number of accumulators and their loads. in the EHC system.
6 @ reservoir skid for transient pressures.
3 @ BPVs for transients. rated to hold (can also open) all bypass valves for 1 min.
4 @ TCVs.
What is the Generator Load Reject?
The load rejection circuitry monitors intermediate pressure (high pressure turbine exhaust pressure as a measure of the turbine energy) and generator stator amperage (as a measure of the energy being produced by the generator). PLU action on valves occurs when the generator current is decreasing at a rate of 1500%/sec. Below 40% of rated intermediate pressure, the PLU circuit cannot actuate.
What are the power supplies for the EHC Logic System?
Logic power in 10C363 is auctioneered between 1AD483 and 10Y107.
1AD483 - Primary logic power and 10C651D HMI
10Y107 - Backup power supply and 10C650E HMI
What happens when a load rejection signal is received?
- The load signal is immediately set to minimum.
- The control valve and intercept valve fast acting solenoids are actuated
- A direct turbine trip is generated.
How does pressure affect RPV level?
Pressure rises, RPV swells.
Pressure lowers, RPV shrinks.
How does RPV pressure affect power?
Pressure rises=> Less boiling due to an increase in saturation temp=> Void content goes down=> More moderation=> Prx goes up.
Pressure lowers=> More violent boiling due to a lower saturation temp=> Void content goes up=> Less moderation=> Prx goes down.
Describe the Turbine Speed Control (S1) coincidence.
2/3 coincidence.
When 1 is lost, alarms and loss of backup, then becomes 1/2 coincidence.
When 2 are lost, the turbine is tripped.
Describe the Turbine Pressure Control (P1) coincidence.
2/3 coincidence.
When 1 is lost, alarms and loss of backup, then becomes 1/2 coincidence.
When 2 are lost, loss of BPV’s and TCV’s a closed.