NSSSS - 1.0 Flashcards
What is the purpose of NSSSS?
The NSSSS develops and initiates isolation signals for the reactor vessel and primary containment isolation valves for systems directly connected to the RPV.
Describe the actuation motive force.
De-energize to actuate
Of the NSSSS channels, what channels are required to trip what components?
1) Inboard Isolation Valves - Channels A and B
2) Outboard Isolation Valves - Channels C and D
3) Main Steam Isolation Valves - Channels A or C and B or D
What does depressing the B or C NSSSS pushbuttons do?
Nothing
What does depressing the B and C NSSSS pushbuttons do?
Close MSIVs
What does depressing the A and D NSSSS pushbuttons do?
Close all NSSSS valves
What channels of NSSSS must actuate to close the MSIVs and Drains?
channels A or C AND B or D
What are the automatic isolation conditions for the MSIV trips?
- RPV Level 1 (-129”)
- Low Condenser Vacuum (21.5” HgA)
- Low MS Line Pressure (Mode Switch in Run and < 756 psig)
- MS Line High Flow (162.8 psid)
- MS Tunnel High Temp (160F)
If a NSSSS trip occurs with the MSIVs and they are shut, what conditions must be met before the valves can be reopened?
Reopening the MSIVs after closure IAW plant procedures, requires MSIV switches be placed in “close”
What are the automatic isolation conditions for the Reactor Recirc Sample Lines (SV-4310(4311) trips?
A & B (C & D) or A (D) manual
* RPV Level 2 (-38”)
* Main Steam Line HI Rad (3.0 x Normal Full Power Background)
What are the automatic isolation conditions for the RWCU Pump Suction Valves trips?
F001 (A & B or A Manual) and F004 (C & D or D Manual)
* RPV Level 2 (-38”)
* Diff Flow Hi (56.3 gpm, 45 sec TD)
* Area Temp Hi
1. 4402 Pipe Chase (160F) – EOP-103 Entry
Condition
2. Pump OR HX Rooms (140F)
3. 4505 Pipe Chase (135F)
* Ventilation Differential Temp (60F)
* SLC Initiation (A Pump – F001 Closes, B Pump –
F004 Closes)
* NRHX outlet 140F (F004 only)
What are the automatic isolation conditions for the RHR S/D Cooling Valves trips?
- RPV Level 3 (+12.5”)
- RPV Press High (82 psig)
Note: SDC valves require an input from A/B (Inboard) or C/D (Outboard) so only an ‘A’ or ‘D’ manual isolation will have any effect. However, since the high pressure trips are only single coincidence, a loss of either RPS bus, will result in all SDC isolation valves closing.
What are the automatic isolation conditions for the RHR Sample and Radwaste (F049/F079(40/80) trips?
A & B (C & D), A (D) Manual)
* RPV Level 3 (+12.5”)
* Hi Drywell Pressure (1.68psig)
Note: These differ from SDC valves only in that the Hi DW Press has coincidence, therefore only a loss of A(D) channels will cause the valves to close.
What are the automatic isolation conditions for the TIP isolations trips?
- RPV Level 2 (-38”)
- Drywell High Pressure (1.68psig)
- Gas Purge Only Isolates on RBV Exhaust 1x10-3uci/cc (Via PCIS, not NSSSS)
What isolates in NSSSS based on 1.68# in the drywell?
Nothing