EDG HVAC - .5 Flashcards

1
Q

“Auto Lead” Start signals (Recirc Fan (412))

A
  1. EDG Starts*
  2. LOP/LOCA Level 1 (Sequenced @ 30 Seconds)
  3. Hi Temp (A-D: 104°F, E-H: 115°F)*
    *Recirc fan will run for ≥ 45 min after starting with EDG running..
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

“Auto” Start signals (Recirc Fan (412))

A
  1. EDG Starts and Hi Temp (A-D: 104°F, E-H: 115°F)*
  2. Low Flow Trip of running fan
  3. LOP/LOCA Level 1 (95 Seconds)
    *Recirc fan will run for ≥ 45 min after starting with EDG running.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

DAS and DAE fan operation during LOP.

A

DAS and DAE fans will lose power during a LOP. However, during a LOP, both DAPRS (Diesel Area Panel Room Supply) fans (408), all switchgear room coolers (401), and all DG room recirc fans (412) will be sequenced on.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

1E battery exhaust fan and heater operation.

A

All of the 1E battery exhaust fans and heaters are 1E powered. They are not sequenced on by the sequencer individually, but will restart when power is returned to their bus (no U/V trip).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly