FRVS Flashcards

1
Q

What are the FRVS fan initiation signals?

A
  1. Drywell pressure (1.68psig)
  2. RPV Level 2 (-38”)
  3. Rx Building Hi Rad (1X10-3uci/cc)
  4. Refuel Floor Hi Rad (2X10-3uci/cc)
  5. Lo Flow (E & F Only, If initiation signal present)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the power supplies for the 6 FRVS recirc fans?

A

2 fans each on A and B channel 1E AC and 1 fan each on the C and D 1E AC buses.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the FRVS recirc fan trips?

A
  1. Lo Flow (18,000 scfm (15,000 – ‘F’) (15 seconds)
  2. Deluge Flow (9 gpm)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the series of events for FRVS initiation?

A
  1. Starts all six recirc fans and 1 vent fan. The E & F fans can be secured after start. These are the only two fans that will restart on a fan trip (If initiation signal is still in)
  2. Starts the FRVS vent fan that is in AUTO Lead (LOCA 19sec TD)
  3. Vent Fan in AUTO will start: [backup to fan in ]
    • Start signal (i.e. not in a surveilence) and
    • Running fan low flow(<6570scfm / 45 sec)
  4. FRVS Vent Fans Trip
    • Low flow (<6570scfm / 30 sec)
    • Deluge system activation
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the LOCA/Hi Rad Actuation sequence for FRVS?

A
  1. RBVS/RBVE 1E breakers trip
  2. RBVS secondary containment isolation dampers close
  3. All six FRVS recirc fans start
  4. The Auto lead [AULD] FRVS vent fan starts
  5. RBVS vent and purge dampers close
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What does swapping control to the RSP do to FRVS?

A

Transfer to RSP opens Secondary Containment isolation dampers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What does it mean if the FRVS recirc fan pushbutton is flashing?

A

FRVS Recirc fan pushbuttons will flash if a start signal was received and the fan is not running.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are FRVS fans rated for?

A

FRVS Recirc fans are rated at 30,000 scfm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What will a closure of the GUD-925(reactor building supply damper) cause?

A

caused the supply fans to trip and will cause reactor building d/p to degrade

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How do you start an FRVS fan in non-emergent conditions?

A
  1. Start 1 FRVS Vent Fan (Manual -> Start -> AULD (place other in auto))
  2. Remove RBVS from service – Stop supply fans then exhaust fans & close dampers.
  3. Start 4 recirc fans.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What FRVS special features exist?

A

C & D SACS Cross Tie Capability
E & F Auto Restart Capability
A - D - Start 6 Seconds after LOCA
E – F – Start 17 Seconds after LOCA
Auto Lead Vent Fan – 19 seconds