Circ Water HVAC Flashcards
What are the CW pump house ventilation fans auto starts?
LOW Speed (30k scfm)
Associated circ. pump is running
AND
Room Temperature > 80ºF
HIGH Speed(60k scfm) OR increase from LOW to HIGH(
Room Temperature > 99°F
Exhaust Fan auto STOPs when Room Temperature <80°F
Describe the operations of the CW HVAC SWGR room running fan trip and auto fan pickup.
Low flow trip at 12k scfm and the standby fan will pick up. It is bypassed for 20 sec after start to allow starting.
Describe operations of the CW HVAC SWGR fan operations.
- Fan intake and recirc dampers adjust to
Regulate room temperature (75F) - 1st stage heaters energize at < 62F
- 2nd stage heaters energize at < 60F
Describe the interlocks associated with the CW HVAC fans.
- Low or high switches cause exhaust fans to run in that speed
- Lower exhaust fans are manual only (via disconnect).
- Pump House Heaters cycle to maintain >40F
What are the CW HVAC pump room and SWGR room fan speeds.
Pump House exh fans are 2 speed (Auto, Stop, Low, High)
Switchgear Room supply fans Auto/Stop/Run