What are the CW pump house ventilation fans auto starts?

A

LOW Speed (30k scfm)
Associated circ. pump is running
AND
Room Temperature > 80ºF

HIGH Speed(60k scfm) OR increase from LOW to HIGH(
Room Temperature > 99°F

Exhaust Fan auto STOPs when Room Temperature <80°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Describe the operations of the CW HVAC SWGR room running fan trip and auto fan pickup.

A

Low flow trip at 12k scfm and the standby fan will pick up. It is bypassed for 20 sec after start to allow starting.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Describe operations of the CW HVAC SWGR fan operations.

A
  • Fan intake and recirc dampers adjust to
    Regulate room temperature (75F)
  • 1st stage heaters energize at < 62F
  • 2nd stage heaters energize at < 60F
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Describe the interlocks associated with the CW HVAC fans.

A
  1. Low or high switches cause exhaust fans to run in that speed
  2. Lower exhaust fans are manual only (via disconnect).
  3. Pump House Heaters cycle to maintain >40F
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the CW HVAC pump room and SWGR room fan speeds.

A

Pump House exh fans are 2 speed (Auto, Stop, Low, High)