Stator Water Cooling - 1.0 Flashcards

1
Q

Under what conditions will the Standby stator water pump start?

A

Low Discharge header pressure
Normal pressure switch setpoints - 107# sensed at the pump discharge and 69# sensed after the heat exchanger and filters. This is equivalent to 730 gpm flow
Backup pressure switch setpoints - 98# sensed at the pump discharge and 64# sensed after the heat exchanger and filters. This is equivalent to 690 gpm flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the power to the standby stator water pump auto starts?

A

Normal pressure switches - 10C120 DC control power
Backup pressure switch - AC Power that comes from the pumps power source

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the SWC pump trips?

A

Unit substation under voltage
Unit differential overcurrent
Generator neutral overcurrent
Generator differential overcurrent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How do you reset the SWC pump trips and why is it important?

A

Must be reset locally in order to remove the tripped condition and run the SWC pumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the conditions that must be met for proper De-ionizer operation?

A

Inlet temp 122F (prevents resin breakdown)
Flow 100gpm (prevents channeling)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What components does the SWC system supply and what are their respective flow rates?

A

811 gpm to stator bars
47 gpm to high voltage bushings (terminal)
100 gpm to deionizer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Under what conditions will the the SWC system initiate a Turbine Generator and Recirc pump full runback and what is the required number of logic inputs?

A

2 of 3 logic
After a 15 sec time delay the following conditions will initiate the protective actions:
Low SWC Inlet Pressure – 64#
Hi SWC Outlet Temp – 79C
Low Flow – 690gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is expected sequence when a Turbine Generator and Recirc pump full runback occurs in response to a SWC system logic signal?

A

15 sec TD
EHC Load set to minimum - if the initiating
condition clears the turbine runback will stop
Additional 12 sec TD (@27 Secs)
Full Recirc runback to 30% occurs - once initiated
it is sealed in and must be manually reset

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

If the main turbine runback is not successful in reducing armature current, under what conditions will the Digital EHC system automatically trip the turbine?

A

> 25 kA for 2 min
7055 A for 3.5 min

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the operator actions if SWC is lost and reactor power is >18%?

A

In 2 minutes the RO must:
REDUCE Recirc pump speed to minimum
LOCK the Mode Switch in Shutdown
Trip the Main Turbine

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What conditions could indicate stator water leak past the stator water-generator gas barrier and what actions should you take if it occurs?

A

If generator pressure drops below 63# you must remove SWC from service to prevent leakage onto the windings.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

If the SWC system is not circulating what are the concerns with the water in the system and what actions must be taken?

A

The generator must be removed from service under the following conditions:
<.5 umho/cm prior to flow loss - 60 min to restore
SWC
.5>x<9.9 umho/cm prior to flow loss - 3 min to
restore SWC
>9.9 umho/cm prior to flow loss - trip turbine
immediately

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

System pressures from low to high.

A

SWCS<Hydrogen<Seal Oil

How well did you know this?
1
Not at all
2
3
4
5
Perfectly